Template 13: Single Hazard - Dual ZoneFACP Configuration Templates

B.7 Template 13: Single Hazard - Dual Zone

TEMPLATE 13: SINGLE HAZARD - DUAL ZONE

 

 

 

 

INPUT ZONES

 

 

 

 

1

2

3

4

5

6

OUTPUT CIRCUITS

 

2-WIRE SMOKE

FIRE

LOW

WATERFLOW

PULL

MANUAL

 

 

 

 

PRESS.

 

STATION

RELEASE

#1 ALARM NAC

 

X

X

 

X

X

X

#2 WATERFLOW NAC

 

 

 

 

X

 

 

#3 RELEASE SOLENOID 1

 

X

X

 

 

X

X

#4 WATERFLOW NAC

 

 

 

 

X

 

 

Table Legend:

X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on corresponding output circuit).

Input Zone Types:

Zone 1 = 2-wire smoke

Zone 2 = Fire

Zone 3 = Low Pressure

Zone 4 = Waterflow - activation delayed for 10 seconds (Waterflow Delay set to 10 secs.)

Zone 5 = Pull Station

Zone 6 = Manual Release

Output Circuit Types:

Output 1 = Alarm NAC

Output 2 = Waterflow NAC - activation delayed for 10 seconds (Waterflow Delay set to 10 secs.)

Output 3 = Release Solenoid 1 (unsupervised for shorts)

Output 4 = Waterflow NAC - activation delayed for 10 seconds (Waterflow Delay set to 10 secs.)

Timers

Soak Timer 1 - set for 10 minutes

Soak Timer 2 - set for 10 minutes

Waterflow Delay Timer - set for 10 seconds

AC Loss Delay Timer - set for 2 hours

Operation

Activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 5 (Pull Station) or Zone 6 (Manual Release) will operate the Alarm NAC Output #1 and Release Solenoid 1 Output #3. Release Solenoid will turn off water release following time-out of the 10 minute Soak Timer 1

Activation of Input Zone 4 (Waterflow) will operate the Alarm NAC Output #1, Waterflow NAC Output #2 and Waterflow NAC Output #4. There is a 10 second FACP initiated delay in activation of these outputs since the Waterflow Delay Timer is set to 10 seconds

Activation of Input Zone 3 (Low Pressure) will not operate any Output Circuits (see Relays)

FACP Relay Operation

The following description of FACP relay operations are in addition to normal system operation.

Alarm Relay - activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 3 (Waterflow - with Waterflow Delay time) or Zone 4 (Manual Release) or Zone 5 (Pull Station) will operate Alarm Relay

Trouble Relay - any system trouble will activate the Trouble Relay

Supervisory - activation of Zone 3 (Low Pressure) will operate the Supervisory Relay

MRP-2001 & MRP-2001E PN 53040:A 4/16/2007