Template 13: Single Hazard - Dual ZoneFACP Configuration Templates
B.7 Template 13: Single Hazard - Dual Zone
TEMPLATE 13: SINGLE HAZARD - DUAL ZONE
|
|
|
| INPUT ZONES |
|
| |
|
| 1 | 2 | 3 | 4 | 5 | 6 |
OUTPUT CIRCUITS |
| FIRE | LOW | WATERFLOW | PULL | MANUAL | |
|
|
|
| PRESS. |
| STATION | RELEASE |
#1 ALARM NAC |
| X | X |
| X | X | X |
#2 WATERFLOW NAC |
|
|
|
| X |
|
|
#3 RELEASE SOLENOID 1 |
| X | X |
|
| X | X |
#4 WATERFLOW NAC |
|
|
|
| X |
|
|
Table Legend:
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on corresponding output circuit).
Input Zone Types:
•Zone 1 =
•Zone 2 = Fire
•Zone 3 = Low Pressure
•Zone 4 = Waterflow - activation delayed for 10 seconds (Waterflow Delay set to 10 secs.)
•Zone 5 = Pull Station
•Zone 6 = Manual Release
Output Circuit Types:
•Output 1 = Alarm NAC
•Output 2 = Waterflow NAC - activation delayed for 10 seconds (Waterflow Delay set to 10 secs.)
•Output 3 = Release Solenoid 1 (unsupervised for shorts)
•Output 4 = Waterflow NAC - activation delayed for 10 seconds (Waterflow Delay set to 10 secs.)
Timers
•Soak Timer 1 - set for 10 minutes
•Soak Timer 2 - set for 10 minutes
•Waterflow Delay Timer - set for 10 seconds
•AC Loss Delay Timer - set for 2 hours
Operation
•Activation of Input Zone 1
•Activation of Input Zone 4 (Waterflow) will operate the Alarm NAC Output #1, Waterflow NAC Output #2 and Waterflow NAC Output #4. There is a 10 second FACP initiated delay in activation of these outputs since the Waterflow Delay Timer is set to 10 seconds
•Activation of Input Zone 3 (Low Pressure) will not operate any Output Circuits (see Relays)
FACP Relay Operation
The following description of FACP relay operations are in addition to normal system operation.
•Alarm Relay - activation of Input Zone 1
•Trouble Relay - any system trouble will activate the Trouble Relay
•Supervisory - activation of Zone 3 (Low Pressure) will operate the Supervisory Relay