Installation

Input Circuits

Combination Waterflow/Supervisory Zone

A combination Waterflow/Supervisory circuit allows an FACP to distinguish between an Alarm switch (waterflow device) and a Supervisory switch (tamper) installed on the same circuit. Any circuit can be programmed as a Combo Type zone. The following figure illustrates the wiring of Zone 2 as a Style B (Class B) Waterflow/Supervisory circuit.

Class B Initiating Device Circuits (supervised and power-limited)

4.7 KΩ, ½ watt resistor P/N:71252

Supervisory Switch (tamper)

In-Line-Resistor

1.2 KΩ, ½ watt resistor P/N: 75579

Alarm Switch

Dummy load all unused

(waterflow)

circuits - 4.7 KΩ, ½ watt

 

resistor (P/N: 71245)

ms10udcomboIDC.cdr

Figure 2.6 Style B Combination Circuit on Zone 2

Requirements for the Combination Waterflow/Supervisory circuit are as follows:

The Waterflow Alarm Switch must connect to the FACP Initiating Device Circuit before the In-Line Resistor as shown in Figure 2.6

The Supervisory Switch must connect to the FACP Initiating Device Circuit after the In- Line Resistor as shown in Figure 2.6

Program the FACP Initiating Device Circuit as a Combination circuit as described in "Input Zones" on page 50. Note that since a Waterflow Supervisory Switch is included in a Combination circuit, the waterflow delay must be taken into consideration. Refer to "Waterflow Delay" on page 66.

Waterflow Alarm Switch activation causes the panel to latch into alarm until the alarm condition is cleared and the FACP is reset

Supervisory Switch activation causes the panel to latch the supervisory condition if the Combo type code is selected or track (the panel will clear when the supervisory condition is cleared) if the Combo Autoresettable Supervisory type code is selected