Input-to-Output Circuit Mapping and Cross-Zone Operation

Circuit Mapping and Cross-Zoning

APPENDIX A

Circuit Mapping and Cross-Zoning

A.1 Input-to-Output Circuit Mapping and Cross-Zone Operation

The flexible cross-zoning and input-to-output (I/O) mapping capability of this fire panel provides a powerful toolset to accommodate many site-specific configurations. To simplify initial setup, preconfigured application templates that employ cross-zoning and I/O mapping are included from the factory. Refer to "FACP Configuration Templates" on page 108 for a description of each supplied template.

The following sections provide some examples of setting up your own cross-zoned or I/O mapped system.

The Installer is responsible for completely testing the proper operation of the fire panel as set

!up by programming. Notes:

1.Any general system trouble, such as a battery fault, will activate any output circuit programmed as TROUBLE NAC in the OUTPUT CIRCUITS menu. Circuit mapping does not apply.

2.Any input zone programmed for supervisory operation or as a DISABLE RELEASE switch in the INPUT CIRCUITS menus will activate any output circuit programmed as SUPV BELL NAC in the OUTPUT CIRCUITS menus. Circuit mapping does not apply.

3.The programming menus will prevent you from mapping any incompatible input zone and output circuit types together, such as mapping a supervisory input zone to a releasing output circuit.

4.Timers and/or delays are not represented in these examples.

MRP-2001 & MRP-2001E PN 53040:A 4/16/2007