Programming | Master Programming Level |
3.5.6.1.1 Soak 1 or Soak 2
The factory default setting for Soak Time is 10 minutes. To select a Soak Time delay of 10 to 30 minutes, press 1 for Soak 1 (Release Circuit 1) or 2 for Soak 2 (Release Circuit 2) while viewing Timer Screen #1. The following display will appear:
TIMER |
|
|
| |
1=SOAK | 1 | 1 | MIN |
|
2=SOAK | 2 | 2 | MIN |
|
3=WATERFLOW DELAY 0 | S | |||
|
|
|
|
|
Timer Screen #1
Soak Time Setup Screen
Pressing 1 while viewing the Soak Time Setup Screen will program the corresponding releasing circuit to remain on during alarm activation until the alarm is cleared and the panel is reset.
Pressing 2 while viewing the Soak Time Setup Screen will display the following screen:
SOAK # TIME
RANGESoak Time Screen
This screen allows the user to program a specific length of time for the releasing circuit to remain active after an input initiating a release has cleared. A flashing cursor is positioned in the lower left corner of the display. Enter a soak time consisting of two digits, such as 10 for ten minutes. Upon entering the second digit, the time delay will be stored in the control panel memory and the display will return to the Delay Screen which will indicate the new soak time. In this example, when the input circuit which initiated a release has cleared, the soak timer will start, allowing the releasing circuit to continue releasing water for a total of ten minutes and then deactivate.
3.5.6.1.2 Waterflow Delay
A delay can be added prior to declaring a waterflow type of alarm. Be careful to include any
Waterflow Delay Screen
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting of two digits, such as 25 for
66 |