Circuit Mapping and |
Using the INPUT ZONES menus, you can assign any input zone to directly activate (without cross- zoning) any of the four output circuits provided they are assigned matching operational types (see the OUTPUT CIRCUIT MAP menu within the INPUT ZONES menus).
Example 1: A waterflow input zone assigned to directly activate an alarm output circuit by setting the OUTPUT CIRCUIT MAP assignment to YES.
•Output Circuit 1 is programmed as alarm NAC using the OUTPUT CIRCUITS menus.
•Output Circuit 2 is programmed as Release Circuit 1 using the OUTPUT CIRCUITS menus.
•Output Circuit 3 is programmed as Release Circuit 2 using the OUTPUT CIRCUITS menus.
•Output Circuit 4 is programmed as supervisory NAC using the OUTPUT CIRCUITS menus.
•Input Zone 1 is programmed as a waterflow zone using the INPUT ZONES menus.
Waterflow Input Zone 1 will directly activate Output Circuit 1 (Alarm NAC) but not Output Circuits 2, 3 or 4.
ZONE 1 TYPE
1=N/A
2=WATERFLOW 3=WATERFLOW NS
OUTPUT MAP ZONE 1
1=ALARM NAC | YES |
2=RELEASE 1 | NO |
3=RELEASE 2 | NO |
| |
| |
OUTPUT MAP ZONE 1 | |
1=SUPV BELL NAC | N/A |
|
|
Example 2: A single hazard application where a smoke detector input zone will directly activate both an alarm NAC circuit and a releasing output circuit.
•Output Circuit 1 is programmed as alarm NAC using the OUTPUT CIRCUITS menus.
•Output Circuit 2 is programmed as Release Circuit 1 using the OUTPUT CIRCUITS menus.
•Output Circuit 3 is programmed as waterflow NAC using the OUTPUT CIRCUITS menus.
•Output Circuit 4 is programmed as supervisory NAC using the OUTPUT CIRCUITS menus.
•Input Zone 1 is programmed as a smoke detector zone using the INPUT ZONES menus.
Smoke detector Input Zone 1 will directly activate Output Circuits 1 (Alarm NAC) and 2 (Release 1) but not output circuits 3 or 4.
ZONE 1 TYPE 1=COMBO
2=COMBO W/AR. SUPERV
OUTPUT MAP ZONE 1
1=ALARM NAC | YES |
2=RELEASE 1 | YES |
3=WATERFLOW NAC | NO |
| |
| |
OUTPUT MAP ZONE 1 | |
1=SUPV BELL NAC | N/A |
|
|
104 |