Circuit Mapping and Cross-Zoning

Input-to-Output Circuit Mapping and Cross-Zone Operation

A.1.1 Mapping Input Zones to Output Circuits for Direct Activation

Using the INPUT ZONES menus, you can assign any input zone to directly activate (without cross- zoning) any of the four output circuits provided they are assigned matching operational types (see the OUTPUT CIRCUIT MAP menu within the INPUT ZONES menus).

Example 1: A waterflow input zone assigned to directly activate an alarm output circuit by setting the OUTPUT CIRCUIT MAP assignment to YES.

Output Circuit 1 is programmed as alarm NAC using the OUTPUT CIRCUITS menus.

Output Circuit 2 is programmed as Release Circuit 1 using the OUTPUT CIRCUITS menus.

Output Circuit 3 is programmed as Release Circuit 2 using the OUTPUT CIRCUITS menus.

Output Circuit 4 is programmed as supervisory NAC using the OUTPUT CIRCUITS menus.

Input Zone 1 is programmed as a waterflow zone using the INPUT ZONES menus.

Waterflow Input Zone 1 will directly activate Output Circuit 1 (Alarm NAC) but not Output Circuits 2, 3 or 4.

ZONE 1 TYPE

1=N/A

2=WATERFLOW 3=WATERFLOW NS

OUTPUT MAP ZONE 1

1=ALARM NAC

YES

2=RELEASE 1

NO

3=RELEASE 2

NO

 

 

OUTPUT MAP ZONE 1

1=SUPV BELL NAC

N/A

 

 

Example 2: A single hazard application where a smoke detector input zone will directly activate both an alarm NAC circuit and a releasing output circuit.

Output Circuit 1 is programmed as alarm NAC using the OUTPUT CIRCUITS menus.

Output Circuit 2 is programmed as Release Circuit 1 using the OUTPUT CIRCUITS menus.

Output Circuit 3 is programmed as waterflow NAC using the OUTPUT CIRCUITS menus.

Output Circuit 4 is programmed as supervisory NAC using the OUTPUT CIRCUITS menus.

Input Zone 1 is programmed as a smoke detector zone using the INPUT ZONES menus.

Smoke detector Input Zone 1 will directly activate Output Circuits 1 (Alarm NAC) and 2 (Release 1) but not output circuits 3 or 4.

ZONE 1 TYPE 1=COMBO

2=COMBO W/AR. SUPERV

3=2-WIRE SMOKE

OUTPUT MAP ZONE 1

1=ALARM NAC

YES

2=RELEASE 1

YES

3=WATERFLOW NAC

NO

 

 

OUTPUT MAP ZONE 1

1=SUPV BELL NAC

N/A

 

 