Master Programming Level

Programming

To change the programming for the displayed zone, press the keyboard ‘down’ arrow key to view the Edit Zone screens.

The following examples show the editing of Input Zone 1:

INPUT ZONE 1=ENABLED 2=TYPE

3=OUTPUT CIRCUIT MAP

Edit Input Zone Screen #2

INPUT ZONE 1

1=ENABLED YES 2=TYPE PULL STATION 3=OUTPUT CIRCUIT MAP

Edit Input Zone Screen #2

INPUT ZONE 1 1=NOUN/ADJECTIVE 2=DESCRIPTION

********************

Edit Input Zone Screen #3

Enable/Disable Zone

To Enable or Disable the zone, press the 1 key while viewing the Edit Input Zone Screen #2. Each press of the key will toggle the screen between Enabled Yes and Enabled No. If Enabled No is selected, the zone will be disabled by the control panel, preventing the circuit from reporting alarms and troubles to the panel. The control panel LCD will display the zone which has been disabled and FACP will turn on the Trouble indicator.

Type

To select the type of zone being programmed, press the 2 key while viewing the Edit Input Zone Screen #2. This will cause the control panel to display the following Zone Type Screen:

ZONE 1 TYPE 1=PULL STATION 2=N/A3=MANUAL RELEASE

Zone Type Screen #1

MRP-2001 & MRP-2001E PN 53040:A 4/16/2007

51