2.3 Input Circuits
The
detector rating of approximately 45oF. The maximum loop resistance limit for each IDC is 100 ohms. The maximum number of detectors per zone is 25. The field wiring for each zone is supervised for opens, shorts and ground faults. All conditions are visually and audibly annunciated.
Each circuit is configured for Style B (Class B) operation and will accept i3 smoke detectors, any
Initiating Device Circuits can be converted to Style D (Class A) by installing the optional Class A Converter module. Refer to
Class B Initiating Device Circuits (supervised and
| UL listed Power Supervision Relay |
| |
(refer to Device Compatibility Document for list of compatible relays) |
| ||
UL listed compatible | Input IDC | ||
|
| ||
| manual pull stations | Waterflow Circuit | |
Resettable 24 VDC | Normally Open | ||
manual | Waterflow | ||
release | Devices or | ||
detector power | |||
heat detectors | Pressure Switches | ||
(500 mA maximum) |
|
|
Dummy load all unused circuits - 4.7 KΩ, ½ watt resistor (P/N: 71245)
Figure 2.5 IDC Connections