FACP Configuration TemplatesTemplate 8: Single Hazard -
B.2 Template 8: Single Hazard - Cross-Zone With Manual Release
TEMPLATE 8:
|
|
|
| INPUT ZONES |
|
|
|
|
| 1 | 2 | 3 | 4 | 5 | 6 |
OUTPUT CIRCUITS |
| FIRE | WATERFLOW | MANUAL | PULL | SUPV. | |
|
|
|
|
| RELEASE | STATION |
|
#1 ALARM NAC |
| X | X |
| X | X |
|
#2 WATERFLOW NAC |
|
|
| X |
|
|
|
#3 RELEASE SOLENOID 1 |
| C1 | C1 |
| X | X |
|
#4 SUPV. BELL NAC |
|
|
|
|
|
| X |
Table Legend:
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on corresponding output circuit).
Cx =
Input Zone Types:
•Zone 1 =
•Zone 2 = Fire
•Zone 3 = Waterflow - activation delayed for 60 seconds (Waterflow Delay set to 60 secs.)
•Zone 4 = Manual Release
•Zone 5 = Pull Station
•Zone 6 = Supervisory
Output Circuit Types:
•Output 1 = Alarm NAC
•Output 2 = Waterflow NAC - activation delayed for 60 seconds (Waterflow Delay set to 60 sec)
•Output 3 = Release Solenoid 1 (unsupervised for shorts)
•Output 4 = Supervisory Bell NAC
Timers
•Soak Timer 1 - set for 10 minutes
•Soak Timer 2 - set for 10 minutes
•Waterflow Delay Timer - set for 60 seconds
•AC Loss Delay Timer - set for 2 hours
Operation
•Activation of both Input Zone 1
4(Manual Release) or Zone 5 (Pull Station) will operate the Release Solenoid 1 Output #3. Release Solenoid will turn off water release following
1.Activation of any one of these zones will operate Alarm NAC Output #1
•Activation of Input Zone 3 (Waterflow) will operate the Waterflow NAC Output #2. There is a 60 second FACP initiated delay in activation since Waterflow Delay Timer is set to 60 seconds
•Activation of Input Zone 6 (Supervisory) will operate the Supervisory Bell NAC Output #4
FACP Relay Operation
The following description of FACP relay operations are in addition to normal system operation.
•Alarm Relay - activation of Input Zone 1
•Trouble Relay - any system trouble will activate the Trouble Relay
•Supervisory - activation of Zone 6 (Supervisory) will operate the Supervisory Relay
110 |