FACP Configuration TemplatesTemplate 8: Single Hazard - Cross-Zone With Manual Release

B.2 Template 8: Single Hazard - Cross-Zone With Manual Release

TEMPLATE 8: CROSS-ZONE WITH MANUAL RELEASE SWITCH

 

 

 

 

INPUT ZONES

 

 

 

 

 

1

2

3

4

5

6

OUTPUT CIRCUITS

 

2-WIRE SMOKE

FIRE

WATERFLOW

MANUAL

PULL

SUPV.

 

 

 

 

 

RELEASE

STATION

 

#1 ALARM NAC

 

X

X

 

X

X

 

#2 WATERFLOW NAC

 

 

 

X

 

 

 

#3 RELEASE SOLENOID 1

 

C1

C1

 

X

X

 

#4 SUPV. BELL NAC

 

 

 

 

 

 

X

Table Legend:

X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on corresponding output circuit).

Cx = cross-zone where x is the number of the Release Solenoid. All inputs with the same Release Solenoid number must be active at the same time to turn on the corresponding solenoid output circuit

Input Zone Types:

Zone 1 = 2-wire smoke

Zone 2 = Fire

Zone 3 = Waterflow - activation delayed for 60 seconds (Waterflow Delay set to 60 secs.)

Zone 4 = Manual Release

Zone 5 = Pull Station

Zone 6 = Supervisory

Output Circuit Types:

Output 1 = Alarm NAC

Output 2 = Waterflow NAC - activation delayed for 60 seconds (Waterflow Delay set to 60 sec)

Output 3 = Release Solenoid 1 (unsupervised for shorts)

Output 4 = Supervisory Bell NAC

Timers

Soak Timer 1 - set for 10 minutes

Soak Timer 2 - set for 10 minutes

Waterflow Delay Timer - set for 60 seconds

AC Loss Delay Timer - set for 2 hours

Operation

Activation of both Input Zone 1 (2-Wire Smoke) and Zone 2 (Fire) at the same time, or Zone

4(Manual Release) or Zone 5 (Pull Station) will operate the Release Solenoid 1 Output #3. Release Solenoid will turn off water release following time-out of the 10 minute Soak Timer

1.Activation of any one of these zones will operate Alarm NAC Output #1

Activation of Input Zone 3 (Waterflow) will operate the Waterflow NAC Output #2. There is a 60 second FACP initiated delay in activation since Waterflow Delay Timer is set to 60 seconds

Activation of Input Zone 6 (Supervisory) will operate the Supervisory Bell NAC Output #4

FACP Relay Operation

The following description of FACP relay operations are in addition to normal system operation.

Alarm Relay - activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 3 (Waterflow - with Waterflow Delay time) or Zone 4 (Manual Release) or Zone 5 (Pull Station) will operate Alarm Relay

Trouble Relay - any system trouble will activate the Trouble Relay

Supervisory - activation of Zone 6 (Supervisory) will operate the Supervisory Relay

110

MRP-2001 & MRP-2001E PN 53040:A 4/16/2007