Master Programming Level

Programming

3.5.7.7 ANN-RLY Options

Pressing 1 for ANN-RLY Options while viewing ANN-BUS Screen #3 will cause the following screen to be displayed:

PROGRAMMING 1=ANN-RLY OPTIONS 2=ANN-LED OPTIONS

ANN-BUS Screen #3

ANN-RLY OPTIONS

1=RELAY 1

IN ZONE 1

2=RELAY

2

IN

ZONE

2

3=RELAY

3

IN

ZONE

3

ANN-RLY Options Screen

The ANN-RLY module provides ten Form-C relays which can be programmed for various functions. The initial screen displays Relays 1 through 3. Pressing the down arrow key will display the remaining relays for this module.

To program any of the ANN-RLY relays, while viewing the appropriate ANN-RLY Option screen, press the number key corresponding to the relay to be programmed. Following is a list of the available programming options for each relay:

General Alarm

General Trouble

General Supervisory

Future Use

Future Use

Future Use

General Discharge

Discharge Release 1

Discharge Release 2

AC Loss

Waterflow Delay

Future Use

Future Use

Future Use

General 2nd Shot Release

2nd Shot Release 1

2nd Shot Release 2

Input Zone 1

Input Zone 2

Input Zone 3

Input Zone 4

Input Zone 5

Input Zone 6

MRP-2001 & MRP-2001E PN 53040:A 4/16/2007

77