Installation | ANN-BUS Devices |
ANN-BUS and power wiring are supervised and power-limited
ANN-80
Figure 2.17 ANN-80 Wiring to FACP
The following table shows the ANN-80 connections to the FACP.
FACP (TB3) | ANN-80 (TB1) |
Terminal 4 GND (-) | Terminal 1 (-) |
Terminal 3 PWR (+) | Terminal 2 (+) |
Terminal 2 A (ANN-BUS) | Terminal 3 (A) |
Terminal 1 B (ANN-BUS) | Terminal 4 (B) |
Programming
Following installation and wiring of the ANN-80 LCD annunciator to the FACP, the annunciator must be added to the system via FACP programming. Refer to the programming section titled "ANN-BUS" on page 71 in this manual for detailed programming information. Select the LCD option for programming.
36 | MRP-2001 & MRP-2001E PN 53040:A 4/16/2007 |