Operating Instructions

Read Status

Alarm/Shorted Condition

When in audible Walktest, the panel responds to each new alarm and activates its programmed control outputs for four seconds, if those outputs have been programmed for silenceable activation. It also stores each alarm in the walktest history file which can be sent to an optional printer. The stored display will be the same as if the device actually activated except the colon (:) in the time stamp is replaced with an asterisk (*).

Open Condition

Addressable devices as well as all main circuit board NACs are monitored for fault conditions during Walktest mode. When a new trouble condition occurs, the FACP will activate all NACs programmed for Walktest, then shut them off after eight seconds.

While in Walktest, the trouble relay is activated and the system Trouble indicator flashes (as in all of the Program and status change operations). The alarm relay is not activated.

4.16 Read Status

Read Status functions do not require a password. The control panel will continue to provide fire protection while in Read Status mode. This mode can be entered while the control panel is in alarm or trouble. If a new alarm occurs during these functions, the Read Status is exited to prevent confusion.

Read Status Entry

When the operator presses the control panel Enter key, the LCD will display the following:

1=READ STATUS MODE 2=PROGRAMMING MODE

Pressing 1, while this screen is being displayed, will cause the control panel to enter the Read Status mode which allows the user to view and print the programmed features and status of the control panel.

The following screens will be displayed:

READ STATUS 1=FACP CONFIG 2=INPUT ZONES 3=OUTPUT CIRCUITS

Read Status Screen #1

READ STATUS

1=CROSS INPUT ZONES 2=ON-BOARD RELAYS 3=SYSTEM SETTINGS

Read Status Screen #2

READ STATUS 1=TIMERS

2=DAYLIGHT SAVINGS 3=HISTORY

Read Status Screen #3

READ STATUS 1=PRINT 2=ANN-BUS

Read Status Screen #4