NFPA 72 Auxiliary Fire Alarm System

NFPA Standard-Specific Requirements

C.1 NFPA 72 Auxiliary Fire Alarm System

All connections are power-limited and supervised. This application is not suitable for separate transmission of sprinkler supervisory or trouble conditions.

Notes:

1.3 ohms maximum loop resistance allowed for wiring from control panel to Municipal Box.

2.Cut JP30 on the MRP-2001/E main circuit board to supervise placement of 4XTMF module and circuit.

3.Cut JP24 on the MRP-2001/E main circuit board to enable FACP Supervisory relay.

4.Refer to "4XTMF Municipal Box Transmitter Option Module" on page 28 for detailed information.

Figure C.2 Municipal Box Connected to 4XTMF Transmitter Module

Polarities shown in alarm condition

FIRE

+

Municipal Box

Circuit -

Gamewell Model M34-56

Local Energy Municipal Box

Nonpower-limited

+ -

4XTMF

Figure A.2 Municipal Box Connected to 4XTMF Transmitter Module

MRP-2001 & MRP-2001E PN 53040:A 4/16/2007