Operating Instructions |
4.9 2nd-Shot Water Switch
Following an initial waterflow release, an input circuit with the nonlatching Type Code of
4.10 Detector Functions
Maintenance Alert
i3 smoke detectors will be polled for maintenance and freeze conditions (temperature less than
45oF) on initial entry into Normal mode. Thereafter, each device will be polled every hour for freeze and every four hours for maintenance conditions All alarm and system trouble conditions are annunciated on the control panel’s LCD.
Note: To ensure that the system is functioning properly, the FACP will perform a freeze check five minutes after the panel is reset, followed by a maintenance check. If there is no freeze or maintenance condition, the panel will continue to monitor for freeze conditions every hour and maintenance conditions every four hours.
Important! In order to avoid false alarms, input zones must be disabled prior to any service work being done. After service is completed, the input zones must be
4.11 Time Functions: Real-Time Clock
The FACP includes a
4.12 Coded NAC Operation
The NAC circuits resident on the control panel main circuit board can be programmed for coded operation. The available options which can be programmed for coded operation are as follows:
•Steady - Steady output with no pulsing
•March Time - Pulses at 120 ppm (pulses per minute)
•California Code - 10 seconds On, 5 seconds Off
•Temporal Code - Pulses at ½ second On, ½ second Off, ½ second On, ½ second Off, ½ second On, 1½ second Off
•
1st zone of a
2nd zone of a
all zones of a
•Synchronized output for System Sensor, Wheelock, Gentex, Faraday or Amseco - Refer to "Synchronized NAC Operation" on page 62 for additional information.
90 |