Installation |
The
•Operating Voltage Range: 18 VDC to 28 VDC
•Current Consumption @ 24 VDC nominal (filtered and nonresettable):
Normal/Standby (no activity): 37.0 mA
Trouble: 39.0 mA
Alarm: 40.0 mA
AC Fail (not backlit): 15.0 mA
•For use indoors in a dry location
2.7.5 InstallationEnsure that all power (AC and DC) has been removed from the FACP before installing the annunciator.
2.7.5.1 Mounting
The
The
2.7.5.2 Opening/Closing Annunciator
The following procedure details the steps used to open the annunciator in order to access the terminal block and DIP switches (refer to figure below):
1.Turn the key switch to the ON (Unlocked) position by turning the key
2.Push in the snap latch located on the right side of the unit while pulling the cover open
3.To close the cover, make certain the key switch is in the ON (Unlocked) position. Swing the cover closed, snapping it shut
4.Turn the key switch to the OFF (Locked) position by turning clockwise and remove the key
Annunciator cover with LCD display | Annunciator backplate |
|
Press in latch and pull annunciator cover open
Key switch shown in ON position
34 |