Installation of Optional Modules

Installation

2.6.2.1 4XTMF Transmitter Module Installation

The 4XTMF provides a supervised output for a local energy municipal box transmitter in addition to alarm and trouble reverse polarity. A jumper option allows the reverse polarity circuit to open with a system trouble condition if no alarm condition exists. A disable switch allows disabling of the transmitter output during testing to prevent accidental calling of the monitoring service.

Local Energy Municipal Box Service (NFPA 72 Auxiliary Fire Alarm Systems): Supervisory Current: 5.0 mA

Trip Current: 350 mA (subtracted from notification appliance power)

Coil Voltage: 3.65 VDC

Maximum Coil Resistance: 14.6 ohms

Maximum allowable wire resistance between panel and trip coil: 3 ohms Municipal Box wiring can leave the building

Remote Station Service (NFPA 72 Remote Station Fire Alarm Systems) - Intended for connection to a polarity reversal circuit or a Remote Station receiving unit having compatible ratings:

Maximum load for each circuit: 10 mA

Reverse polarity output voltage: 24 VDC

Remote Alarm and Remote Trouble wiring can leave the building

Before installing the module, place the disconnect switch to the down (disconnect) position to prevent accidental activation of the municipal box. Note that a Disconnect LED will illuminate after the module is installed in the FACP. In addition, the System Trouble indicator will turn on to indicate the Disconnect condition.

Note: 4XTMF Module is not directly suitable for transmitting reverse polarity supervisory signal. For an application using reverse polarity of a supervisory signal, refer to the Appendix titled "FACP with Keltron" on page 123.

TBL Jumper

TBL

J1

Disconnect Switch

shown in J2 disconnect position

 

 

 

 

 

 

 

Polarities are shown for module activation

TB1

 

 

 

1+

 

 

 

}Remote Alarm (power-limited)*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2-

 

 

 

 

 

 

 

 

 

 

3+

 

 

 

}Remote Trouble (power-limited)*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4-

 

 

 

 

 

 

 

 

 

 

5

 

 

 

 

No connection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6+

 

 

 

}Municipal Box (nonpower-limited)*

 

 

 

 

 

 

 

 

 

 

 

 

 

7-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Wiring from these terminals can exit the protected premises. Dummy load terminals 6 and 7 (4.7kΩ, ¼ watt resistor) if Municipal Box is not connected.

4xtmf.cdr

Disconnect LED

Connect to FACP Connectors J4 & J5

Figure 2.14 4XTMF Transmitter Module

MRP-2001 & MRP-2001E PN 53040:A 4/16/2007