Template 11: Single Hazard - 3 Zones and Low PressureFACP Configuration Templates
B.5 Template 11: Single Hazard - 3 Zones and Low Pressure
TEMPLATE 11: SINGLE HAZARD - 3 ZONES AND LOW PRESSURE
|
|
|
| INPUT ZONES |
|
|
|
|
| 1 | 2 | 3 | 4 | 5 | 6 |
OUTPUT CIRCUITS |
| FIRE | WATERFLOW | MANUAL | PULL | LOW | |
|
|
|
|
| RELEASE | STATION | PRESS. |
#1 ALARM NAC |
| X | X |
| X | X |
|
#2 WATERFLOW NAC |
|
|
| X |
|
|
|
#3 SUPV. BELL NAC |
|
|
|
|
|
| X |
#4 RELEASE SOLENOID 1 |
| X | X |
| X | X |
|
Table Legend:
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on corresponding output circuit).
Input Zone Types:
•Zone 1 =
•Zone 2 = Fire
•Zone 3 = Waterflow - activation delayed for 10 seconds (Waterflow Delay set to 10 secs.)
•Zone 4 = Manual Release
•Zone 5 = Pull Station
•Zone 6 = Low Pressure
Output Circuit Types:
•Output 1 = Alarm NAC
•Output 2 = Waterflow NAC - activation delayed for 10 secs. (Waterflow Delay set to10 secs.)
•Output 3 = Supervisory Bell NAC
•Output 4 = Release Solenoid 1 (unsupervised for shorts)
Timers
•Soak Timer 1 - set for 10 minutes
•Soak Timer 2 - set for 10 minutes
•Waterflow Delay Timer - set for 10 seconds
•AC Loss Delay Timer - set for 2 hours
Operation
•Activation of Input Zone 1
•Activation of Input Zone 3 (Waterflow) will operate the Waterflow NAC Output #2. There is a 10 second FACP initiated delay in activation since Waterflow Delay Timer is set to 10 seconds
•Activation of Input Zone 6 (Low Pressure) will operate the Supervisory Bell NAC Output #3
FACP Relay Operation
The following description of FACP relay operations are in addition to normal system operation.
•Alarm Relay - activation of Input Zone 1
•Trouble Relay - any system trouble will activate the Trouble Relay
•Supervisory - activation of Zone 6 (Supervisory) will operate the Supervisory Relay
113 |