Maintenance | Testing & Maintenance |
Test i3 Series detectors as follows:
Test Switch
1.An opening for the recessed test switch is located on the detector housing.
2.Insert a small screwdriver or allen wrench (0.18” max.) into the test switch opening; push and hold.
3.If the detector is within the listed sensitivity limits, the detector’s red LED should light within five seconds.
Smoke Entry Test
Hold a smoldering punk stick or cotton wick at the side of the detector and gently blow the smoke through the detector until it alarms.
Note: For the above tests, the detector will reset only after the power source has been momentarily interrupted.
If a detector fails any of the above test methods, its wiring should be checked and it should be cleaned as outlined in the Maintenance section of the System Sensor Document. If the detector still fails, it should be replaced.
Notify the proper authorities when the system is back in service.
E.2 Maintenance
A regular schedule of inspection, testing and maintenance is vital to ensure proper and reliable operation of the control panel. The procedures should be performed as required by the local authority having jurisdiction. Refer to NFPA documentation for further details.
125 |