Product Features

SECTION 1

Product Description

Product Description

The MRP-2001 is a six zone FACP for single and dual hazard deluge and preaction applications. The FACP provides reliable fire detection, signaling and protection for commercial, industrial and institutional buildings requiring water-based releasing. The FACP is compatible with System Sensor’s i3 detectors which are conventional smoke detectors that can transmit a maintenance trouble signal to the FACP indicating the need for cleaning and a supervisory ‘freeze’ signal when the ambient temperature falls below the detector rating of approximately 45o F (refer to System Sensor for i3 Installation and Maintenance Instructions). In addition, the control panel is compatible with conventional input devices such as two-wire smoke detectors, four-wire smoke detectors, pull stations, waterflow devices, tamper switches and other normally-open contact devices. Refer to Device Compatibility Document for a complete listing of compatible devices.

Four outputs are programmable as NACs (Notification Appliance Circuits) or releasing solenoids. Three programmable Form-C relays (factory programmed for Alarm, Trouble and Supervisory) and 24 VDC special application resettable and nonresettable power outputs are also included on the main circuit board. The FACP supervises all wiring, AC voltage, battery charger and battery level.

Activation of a compatible smoke detector or any normally-open fire alarm initiating device will activate audible and visual signaling devices, illuminate an indicator, display alarm information on the panel’s LCD, sound the piezo sounder at the FACP, activate the FACP alarm relay and operate an optional module used to notify a remote station or initiate an auxiliary control function.

The MRP-2001E offers the same features as the MRP-2001 but allows connection to 220/240 VAC. Unless otherwise specified, the information in this manual applies to both the 110/120 VAC and 220/240 VAC versions of the panels.

1.1Product Features

Six programmable Style B (Class B) IDCs (Initiating Device Circuit)

Four programmable Style Y (Class B) output circuits - (special application power)

Three programmable Form-C relays

• 7.0 amps total 24 VDC output current

• Resettable and non-resettable output power

Built-in Programmer

ANN-BUS for connection to optional:

ANN-80 Remote LCD Annunciator

 ANN-I/O LED Driver

 ANN-S/PG Printer Module

ANN-RLY Relay Module

ANN-LED Annunciator Module

80-character LCD display (backlit)

Real-time clock/calendar with daylight savings time control

History log with 256 event storage

MRP-2001 & MRP-2001E PN 53040:A 4/16/2007