Time Simplex

Load

Supply

Power

3

Load

Supply

Power

3

 

 

 

19

 

Customer Supplied

 

 

 

 

Electromechanical relay

 

L1

+

20

+

+

 

L2/N

Output #1

21

 

 

1

 

4

 

22

 

Relay Load

N.C. Alarm

Customer Supplied

5

Relay#2

23

Solid-State relay

To terminal

N.O.

 

 

6

 

24

 

 

4 or 6

 

 

25

 

 

Relay Load

7

N.C. Alarm

 

 

8

Relay#1

26

 

 

 

N.O.

 

 

To terminal

9

 

27

 

 

7 or 9

 

 

 

 

 

 

 

 

 

 

 

 

Time Duplex

 

 

Customer Supplied

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

19

 

Electromechanical relay

 

 

 

 

 

 

 

+

 

+

 

 

 

 

L1

 

 

20

+

 

 

 

 

 

Output #1

 

Customer Supplied

 

L2/N

 

 

1

21

 

 

 

 

Electromechanical relay

 

4

 

 

 

22

Customer Supplied

 

+

 

 

+

 

 

 

 

+

5

 

 

23

Solid-State relay

 

 

 

Output #2

 

 

 

 

6

1

2

24

 

 

 

Customer Supplied

 

 

 

 

 

 

 

 

 

7

 

 

 

25

 

 

Load

 

Solid-State relay

 

 

N.C. Alarm

 

 

 

Relay Load

 

8

 

 

Relay#1

26

 

 

Supply

 

 

 

 

N.O.

 

 

 

To terminal

9

 

27

 

 

Power

 

 

 

 

 

 

 

7 or 9

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

1

CAUTION

Open collector outputs are internally powered at +30 Vdc. Connecting an external power supply will damage the controller.

2 Alarm #2 is not available with Time Proportional Duplex or Three Position Step Control unless the Dual Relay option is used.

3Electromechanical relays are rated at 5 Amps @ 120 Vac or 240 Vac or 30 Vdc. Customer should size fuses accordingly. Use Fast Blo fuses only.

Figure 2-10 Open Collector Output

See Table 2-5for relay terminal connections for other Output Algorithm Types.

18

UDC3200 Universal Digital Controller Operator Manual

04/08

Page 24
Image 24
Honeywell UDC3200 manual Open Collector Output