Function

Selections or

Prompt

Range of Setting

Lower Display

Upper Display

EU/HR DN

0 to 9999 in

 

engineering units

 

per hour

 

 

Parameter Definition

RATE DOWN—Rate down value. When making a setpoint change, this is the rate at which the controller will change from the original setpoint down to the new one. The ramping (current) setpoint can be viewed as SPn in the lower display.

Entering a 0 will imply an immediate step change in Setpoint (i.e., no rate applies).

SP PROG

(optional

feature)

DISABLE

ENABLE

STRT SEG

1 to 11

END SEG

2 to 12 even

 

numbers

RAMPUNIT

 

 

TIME

 

EU/MIN

 

EU/HR

 

 

RECYCLES

0 to 99 recycles

 

 

SOAK DEV

0 to 99

 

 

PROG END

LASTSP

 

 

F SAFE

 

 

STATE

DISABLE

 

HOLD

 

 

KEYRESET

DISABLE

 

ToBEGIN

 

RERUN

 

 

HOTSTART

DISABLE

 

ENABLE

 

 

SEG1RAMP or

0-99 hours.0-59

SEG1RATE

minutes

 

Engineering

 

units/minute or

 

Engineering

 

units/hour

 

 

SEG2 SP

Within the Setpoint

 

limits

SETPOINT RAMP/SOAK PROGRAM—Available only with controllers that contain this option.

SP RAMP must be disabled.

DISABLE—Disables setpoint programming.

ENABLE—Enables setpoint programming.

SP Ramp must be disabled for SP Program prompts to appear. If SP Rate is enabled, it does not operate while an SP Program is running

Start Segment Number

End Segment Number, always end in a soak segment (2, 4, ... 12)

RAMPUNIT—Engineering Units for Ramp Segments

TIME in hours: minutes

RATE in Enineering units per minute RATE in Enineering units per hour

Number of Program Recycles

Guaranteed Soak Deviation Value

The number selected will be the PV value (in engineering units) above or below the setpoint outside of which the timer halts.

Program Termination State

Hold at last setpoint in the program

Manual mode/Failsafe output

Program State at Program End

Reset/Rerun SP Program

Hot Start

Segment #1 Ramp Time or

Segment #1 Ramp Rate

Select TIME, EU/MIN, or EU/HR at prompt RAMPUNIT. All ramps will use the same selection.

Segment #2 Soak Setpoint Value

30

UDC3200 Universal Digital Controller Operator Manual

04/08

Page 36