Function | Selections or |
Prompt | Range of Setting |
Lower Display | Upper Display |
RSP SRC |
|
| NONE |
| INPUT 2 |
| IN ALG1 |
AUTOBIAS
DISABLE
ENABLE
SP TRACK
NONE
PV
RSP
PWR MODE
MANUAL
ALSP
A RSP
AM SP
AM LSP
PWR OUT
For Three
Position Step
Control Only
Parameter Definition
REMOTE SETPOINT
INPUT
IN
ATTENTION To cycle through the available local setpoints and
remote setpoint, press and hold in the key. When the key is released, the setpoint selection currently displayed will be the new setpoint selection.
AUTOBIAS is used for bumpless transfer when transferring from local setpoint to remote setpoint. Auto Bias calculates and adds a bias to remote setpoint input each time a transfer is made. Only available if no tracking is selected.
SETPOINT
ATTENTION For selections other than NONE, LSP is stored in nonvolatile memory only when there is a mode change; i.e., when switching from RSP to LSP or from Manual to Automatic. If power is lost, then the current LSP value is also lost.
NO
POWER UP CONTROLLER MODE
MANUAL,
AUTOMATIC MODE, LAST
AUTOMATIC MODE, LAST
LAST MODE/LAST SETPOINT used before power down. LAST MODE/LAST LOCAL SETPOINT on power down.
THREE POSITION CONTROL STEP OUTPUT
04/08 | UDC3200 Universal Digital Controller Operator Manual | 49 |