Image 86

Lower

Reason for Failure

Display

 

PV LIMIT

PV out of range.

 

PV = INP1 x RATIO1+ INP1 BIAS

 

 

RV LIMIT

The result of the formula shown below is

 

beyond the range of the remote variable.

 

RV = INP2 X RATIO + BIAS

 

 

SEGERR

Setpoint Program start segment number is

 

less than ending segment number.

 

 

CAL MTR

Slidewire calibration never performed.

 

 

SW FAIL

Position Proportional slidewire input failure.

 

 

SOOTING

Percent Carbon falls outside sooting

 

boundary

 

 

TCx WARN

Thermocouple on Input x (1 or 2) is

 

starting to burnout.

 

 

TCxFAIL

The Thermocouple on Input x (1 or 2) is in

 

imminent danger of burning out.

 

 

CURFAIL

Current Output is less than 3.5 mA.

 

 

AXFAIL

Auxiliary Output is less than 3.5 mA.

 

 

How to Correct the Problem

1.Make sure the input signal is correct.

2.Make sure the Ratio and Bias settings are correct.

3.Recheck the calibration. Use Bias of 0.0

1.Make sure the input signal is correct.

2.Make sure the Ratio2 and Bias2 settings are correct.

3.Recheck the calibration. Use a Ratio2 of 1.0 and a Bias2 of 0.0.

Check SP Program configuration, subsection 3.4 Set up Group SPPROG function prompts “STRSEG” and “ENDSEG”.

Field Calibrate the slidewire.

Check the slidewire.

Check process for correct operation.

This diagnostic message means that the controller has detected that the thermocouple is starting to burnout. This error message may also be created if the resistance of the wires used to connect the thermocouple to the instrument is above 100 ohms.

This diagnostic message means that the controller has detected that the thermocouple will soon fail. User should consider replacing the thermocouple as soon as possible. This message will also be generated if the resistance of the wires used to connect the thermocouple to the instrument is above 180 ohms.

The current output is open circuit. Check the field wiring.

The auxiliary output is open circuit. Check the field wiring.

80

UDC3200 Universal Digital Controller Operator Manual

04/08