Function

Selections or

Prompt

Range of Setting

Lower Display

Upper Display

RSET2MIN

0.02 to 50.00

RSET2RPM

 

 

 

CYC SEC

1 to 120

or

 

CYC SX3

 

CYC2 SEC

1 to 120

or

 

CYC2 SX3

 

SECURITY

0 to 9999

LOCKOUT

NONE

CALIB

+ CONF

+ VIEW

MAX

Parameter Definition

These are the same as above except that they apply to Duplex models for the "COOL" zone of Heat/Cool applications or for the second set of PID constants.

CYCLE TIME (HEAT) determines the length of one time proportional output relay cycle. Defined as "HEAT" cycle time for Heat/Cool applications.

CYC SEC—Electromechanical relays

CYC SX3—Solid state relays

ATTENTION Cycle times are in either second or 1/3-second increments depending upon the configuration of RLY TYPE in the Output Algorithm Set Up group.

CYCLE TIME 2 (COOL) is the same as above except it applies to Duplex models as the cycle time in the "COOL" zone of Heat/Cool applications or for the second set of PID constants.

CYC2 SEC—Electromechanical relays

CYC2 SX3—Solid state relays

ATTENTION Cycle times are in either second or 1/3-second increments depending upon the configuration of RLY TYPE in the Output Algorithm Set Up group.

SECURITY CODE—The level of keyboard lockout may be changed in the Set Up mode. Knowledge of a security code may be required to change from one level to another. This configuration should be copied and kept in a secure location.

NOTE: The Security Code is for keyboard entry only and is not available via communications.

ATTENTION Can only be changed if LOCKOUT selection is NONE.

LOCKOUT applies to one of the functional groups: Configuration, Calibration, Tuning, Accutune. DO NOT CONFIGURE UNTIL ALL

CONFIGURATION IS COMPLETE.

NONE—No lockout; all groups are read/write.

CALIB—All groups are available for read/write except for the Calibration and Keyboard Lockout groups.

+CONF—Tuning, SP Ramp, and Accutune groups are read/write. All other groups are read only. Calibration and Keyboard Lockout groups are not available.

+VIEW—Tuning and Setpoint Ramp parameters are read/write. No other parameters are viewable.

MAX—Tuning and Setpoint Ramp parameters are available for read only. No other parameters are viewable.

04/08

UDC3200 Universal Digital Controller Operator Manual

27