Honeywell UDC3200 manual IN2 High, IN2 LOW, Bias IN2, Burnout Burnout Protection Sensor Break

Models: UDC3200

1 90
Download 90 pages 12.89 Kb
Page 52
Image 52

Function Prompt

Selections or

Parameter

Lower Display

Range of Setting

Definition

 

Upper Display

 

IN2 HIGH

–999. To 9999. Floating

INPUT 2 HIGH RANGE VALUE in engineering units

 

(in engineering units)

is displayed for all inputs but can only be configured

 

 

for linear or square root transmitter characterization

 

 

See the example in IN1 HI.

 

 

 

IN2 LOW

–999. To 9999. Floating

INPUT 2 LOW RANGE VALUE in engineering units

 

(in engineering units)

is displayed for all inputs but can only be configured

 

 

for linear or square root transmitter characterization.

 

 

See the example in IN1 HI

 

 

 

RATIO 2

–20.00 to 20.00

RATIO ON INPUT 2—Select the Ratio value you

 

Floats to 3 decimal places

want on Input 1.

 

 

 

BIAS IN2

–999. to 9999.

BIAS ON INPUT 2 — Bias is used to compensate

 

(in engineering units)

the input for drift of an input value due to

 

 

deterioration of a sensor, or some other cause.

 

 

Select the bias value you want on Input 1.

 

 

 

FILTER 2

0 to 120 seconds

FILTER FOR INPUT 2—A software digital filter is

 

No filter = 0

provided for Input 1 to smooth the input signal. You

 

 

can configure the first order lag time constant from 1

 

 

to 120 seconds. If you do not want filtering, enter 0.

 

 

 

BURNOUT

 

BURNOUT PROTECTION (SENSOR BREAK)

 

 

provides most input types with upscale or downscale

 

 

protection if the input fails.

 

NONE

NO BURNOUT—If Input 2 is being used in the

 

 

Control Algorithm (such as the PV or RSP input

 

 

parameter), then the pre-configured Failsafe output

 

 

(selected in the CONTROL Set up Group) is applied

 

 

when a failed input is detected (does not apply for an

 

 

input out of range). Diagnostic message IN2 FAIL is

 

 

intermittently flashed on the lower display.

 

UP

UPSCALE BURNOUT will force the Input 2 signal to

 

 

the full scale value when the sensor fails. Diagnostic

 

 

message IN2 FAIL intermittently flashed on the lower

 

 

display.

 

 

The controller remains in Automatic control mode

 

 

and adjusts the controller output signal in response

 

 

to the full scale Input 2 signal developed by the

 

 

Burnout circuitry.

 

DOWN

DOWNSCALE BURNOUT will force the Input 2

 

 

signal to the lower range value when the sensor

 

 

fails. Diagnostic message IN2 FAIL intermittently

 

 

flashed on the lower display.

 

 

The controller remains in Automatic control mode

 

 

and adjusts the controller output signal in response

 

 

to the lower range Input 2 signal developed by the

 

 

Burnout circuitry.

 

 

 