3.7 Output Set Up Group
Function | Selections or |
Prompt | Range of Setting |
Lower Display | Upper Display |
OUT ALG |
|
TIME
CURRENT
POSITON
TIME D
CUR D
CUR TI
TI CUR
OUT RNG
50 PCT
Parameter Definition
The OUTPUT ALGORITHM lets you select the type of output you want. Not applicable with Control algorithm prompt 3PSTEP. Selections are hardware dependent.
ATTENTION For all Duplex Output forms, PID heat parameters apply for controller output greater than 50 %; PID cool parameters apply for controller output less than 50 %.
TIME
CURRENT
POSITION
This output algorithm selection forces Input 2 to the SLIDEW selection when the Control Algorithm is any selection other than 3PSTEP.
ATTENTION Other prompts affected: DEADBAND, IN2 TYPE
TIME
CURRENT DUPLEX is similar to current simplex but uses a second current output. The second output is usually scaled so that zero and span correspond with 0 % and 50 % output (cool zone). When the output is 0 % to 50 %, the controller uses tuning parameter set #2, when the output is 50 % to 100 % it uses set #1.
ATTENTION Other prompts affected: OUT RNG
CURRENT/TIME DUPLEX is a variation of duplex with current active for 0 % to 50 % output (tuning set 2) and time is active 50 % to 100 % output (tuning set 1).
Relay controls heat, current controls cool.
ATTENTION Other prompts affected: OUT RNG
TIME CURRENT DUPLEX is similar to CUR TI except that current is active for 50 % to 100 % and time is active for 0 % to 50 %. Relay controls cool, current controls heat.
ATTENTION Other prompts affected: OUT RNG
CURRENT DUPLEX RANGE ALGORITHM — Used with Output Algorithm selections CUR D, CUR TI, or TI CUR.
CURRENT DUPLEX RANGE