4.5.3 Using AUTOMATIC TUNE at start-up for Duplex (Heat/Cool)

Used when DUPLEX has been configured for AUTOMATIC. This is the preferred selection for most Heat/Cool applications when tuning a new chamber. This selection will sequentially perform both Heat and Cool tuning without further operator intervention.

Table 4-6 Procedure for Using AUTOMATIC TUNE at Start-up for Duplex

Control

Step

Operation

 

Press

Result

1

Configure LSP1

 

 

 

Until SP (Local Setpoint 1) shows

 

Lower

 

 

 

 

Display

 

in the lower display.

 

 

 

 

 

2

 

 

or

 

Until LSP1 is a value within the

 

 

 

 

 

Heat Zone (output above 50%).

3

Configure LSP2

 

 

 

Until 2SP (Local Setpoint 2) shows

 

Lower

 

 

 

 

Display

 

in the lower display.

 

 

 

 

 

4

 

 

or

 

Until LSP2 is a value within the

 

 

 

 

 

Cool Zone (output below 50%).

5

Switch to

 

 

 

Until the “A” indicator is lighted (on

 

Man

 

 

“Automatic” Mode

 

Auto

 

controllers with Manual option).

 

 

 

 

 

6

Show Tuning

 

 

 

Until “TUNE OFF” is shown on

 

Lower

 

 

Prompt

 

Display

 

lower display.

 

 

 

 

 

7

Initiate Tuning

 

 

 

Select “DO SLOW” or “DO FAST”

 

 

 

 

 

in lower display.

 

Tuning in operation

 

 

 

Upper display will show a “T” as

 

 

Lower

 

 

 

 

Display

 

long as ACCUTUNE process is

 

 

 

 

 

operating. When process

 

 

 

 

 

completes, tuning parameters are

 

 

 

 

 

calculated and lower display will

 

 

 

 

 

show “NO TUNE” prompt.