Function

Selections or

Prompt

Range of Setting

Lower Display

Upper Display

MOTOR TI

5 to 1800 seconds

CUR OUT

 

DISABLE

 

INPUT 1

 

INPUT 2

 

PV

 

DEV

 

OUTPUT

 

SP

 

LSP

 

RSP

 

IN ALG 1

LOW VAL

Low Scale Value

 

within the range of

 

the selected

 

variable to

 

represent the

 

minimun output (0

 

or 4 mA)

 

 

HIGH VAL

High Scale Value

 

within the range of

 

the selected

 

variable to

 

represent the

 

maximum output

 

(20 mA)

 

 

CO RANGE

4-20mA

 

0-20mA

Parameter Definition

MOTOR TIME – Appears only when “POSITON” is selected as the Output algorithm. This is the time it takes the motor to travel from 0 to 100% (fully closed to fully open). This time can usually be found on the nameplate of the motor.

CURRENT OUTPUT – If Current Output #1 is not used to perform one of the above output algorithms, it may be used to perform an Auxiliary Output function.

DISABLE

INPUT 1

INPUT 2

PV (Process Variable)

DEVIATION

OUTPUT

SETPOINT

LOCAL SETPOINT

REMOTE

INPUT ALGORITHM 1

CURRENT OUTPUT LOW SCALING FACTOR—Used only when CUR OUT is any selection other than DISABLE. This is a value in engineering units used to represent all CUR OUT parameters except Output.

For Output, this is a value in percent and can be any value between –5 % and +105 %. However, keep in mind that relay output types can only be scaled 0 % to 100 %.

CURRENT OUTPUT HIGH SCALING FACTOR—Used only when CUR OUT is any selection other than DISABLE. This is a value in engineering units used to represent all CUR OUT parameters except Output.

For Output, this is a value in percent and can be any value between –5 % and +105 %. However, keep in mind that relay output types can only be scaled 0 % to 100 %.

CURRENT OUTPUT RANGE allows the user to easily select 4-20 mA output or 0-20 mA output operation without the need for recalibration of the instrument.

ATTENTION Changing the Current Output Range will result in the loss of Field Calibration values and will restore Factory Calibration values.

04/08

UDC3200 Universal Digital Controller Operator Manual

41

Page 47
Image 47