3.4 SP Ramp Set Up Group
Function | Selections or |
Prompt | Range of Setting |
Lower Display | Upper Display |
SP RAMP |
|
SP Program |
|
must be |
|
disabled for SP |
|
Ramp prompts | DISABLE |
to appear | |
| ENABLE |
|
|
TIME MIN | 0 to 255 minutes |
|
|
FINAL SP | Within setpoint |
| limits |
HOTSTART DISABLE
ENABLE
Parameter Definition
SINGLE SETPOINT
SP Programming must be disabled.
DISABLE SETPOINT
ENABLE SETPOINT
SETPOINT RAMP
SETPOINT RAMP FINAL
ATTENTION If the ramp is on HOLD, the held setpoint can be changed by the ▲ and ▼ keys. However, the ramp time remaining and original ramp rate is not changed. Therefore, when returning to RUN mode, the setpoint will ramp at the same rate as previous to the local setpoint change and will stop if the final setpoint is reached before the time expires. If the time expires before the final setpoint is reached, it will jump to the final setpoint.
ATTENTION SP RAMP and SP RATE will cause the SP portion of Accutune to abort. PV Tune will continue to function normally. Ramp is placed into HOLD while tuning (TUNE configuration).
SP RATE
DISABLE
ENABLE
EU/HR UP | 0 to 9999 in |
| engineering units |
| per hour |
SETPOINT
DISABLE SETPOINT
ENABLE SETPOINT
SP Rate operates only when both SP Ramp and SP Programing are in HOLD mode or when both SP Ramp and SP Programming are disabled.
RATE
Entering a 0 will imply an immediate step change in Setpoint (i.e., no rate applies).
04/08 | UDC3200 Universal Digital Controller Operator Manual | 29 |