Function | Selections or |
Prompt | Range of Setting |
Lower Display | Upper Display |
XMITTER | B TC |
| E TC H |
| E TC L |
| J TC H |
| J TC M |
| J TC L |
| K TC H |
| K TC M |
| K TC L |
| NNM H |
| NNM L |
| NIC H |
| NIC L |
| R TC |
| S TC |
| T TC H |
| T TC L |
| W TC H |
| W TC L |
| 100 PT |
| 100 LO |
| 200 PT |
| 500 PT |
| RAD RH |
| RAD RI |
| LINEAR |
| SQROOT |
IN1 HIGH | |
| Floating |
| (in engineering |
| units) |
IN1 LOW | |
| Floating |
| (in engineering |
| units) |
RATIO 1 | |
| Floats to 3 decimal |
| places |
|
|
BIAS IN1 | |
| (in engineering |
| units) |
|
|
FILTER 1 | 0 to 120 seconds |
| No filter = 0 |
Parameter Definition
TRANSMITTER
ATTENTION Prompt only appears when a linear actuation is selected at prompt IN1 TYPE.
FOR EXAMPLE:
If input 1 is a 4 to 20 mA signal, but the signal represents a type K H thermocouple, then configure K TC H and the controller will characterize the 4 to 20 mA signal so that it is treated as a type K thermocouple input (high range).
Parameter definitions are the same as in IN1 TYPE.
INPUT 1 HIGH RANGE VALUE in engineering units is displayed for all inputs but can only be configured for linear or square root transmitter characterization.
Scale the #1 input signal to the display value you want for 100 %.
ATTENTION The control setpoint will be limited by the range of units selected here.
INPUT 1 LOW RANGE VALUE in engineering units is displayed for all inputs but can only be configured for linear or square root transmitter characterization. Scale the #1 input signal to the display value you want for 0 %. See example above.
ATTENTION The control setpoint will be limited by the range of units selected here.
RATIO ON INPUT
BIAS ON INPUT 1 — Bias is used to compensate the input for drift of an input value due to deterioration of a sensor, or some other cause. Select the bias value you want on Input 1.
FILTER FOR INPUT
04/08 | UDC3200 Universal Digital Controller Operator Manual | 43 |