Honeywell UDC3200 manual Accutune Set Up Group, Fuzzy Disable Enable Accutune Tune, AT Error

Models: UDC3200

1 90
Download 90 pages 12.89 Kb
Page 38
Image 38

3.5 Accutune Set Up Group

Function

Selections or

Prompt

Range of Setting

Lower Display

Upper Display

FUZZY

 

 

DISABLE

 

ENABLE

 

 

ACCUTUNE

 

 

DISABLE

 

TUNE

DUPLEX

 

This prompt

 

only appears

MANUAL

when a Duplex

Control

 

Algorithm has

 

been

 

configured

AUTO

 

DISABLE

AT ERROR

(Read Only)

NONE

RUNNING

ABORT

SP2

Parameter Definition

FUZZY OVERSHOOT SUPPRESSION—Can be enabled or disabled independently of whether Demand Tuning or SP Tuning is enabled or disabled.

DISABLE—Disables Fuzzy Overshoot Suppression.

ENABLE—The instrument uses Fuzzy Logic to suppress or minimize any overshoot that may occur when PV approaches SP. It will not recalculate any new tuning parameters.

ACCUTUNE III

DISABLE —Disables the Accutune function.

DEMAND TUNING—If TUNE is selected, and tuning is initiated through the operator interface or digital input (if configured), the algorithm calculates new tuning parameters and enters them into the tuning group. This tuning requires no process knowledge and does not require line out for initialization.

DUPLEX ACCUTUNING III – These prompts only appear when a duplex output type has been configured.

MANUAL – Tune manually using LSP 1 and LSP 2 values. LSP 1 is used to derive tuning parameters associated with HEAT (output

>50 %). LSP 2 is used to derive tuning parameters associated with COOL (output < 50 %).

AUTOMATIC – Tuning is performed automatically on both HEAT and COOL sequentially. LSP 1 is used for HEAT tuning and LSP 2 is used for COOL tuning. To initiate tuning, either LSP 1 or LSP 2 must be in use.

DISABLE – The current SetPoint is used to derive a single set of blended tuning parameters. This tuning is performed over the range of the output limits similar to Simplex Tuning. The Tuning Parameters derived are placed into both the HEAT and COOL tune sets (PID 1 and PID 2).

ACCUTUNE ERROR STATUS—When an error is detected in the Accutune process, an error prompt will appear.

NONE—No errors occurred during last Accutune procedure.

RUNNING—An Accutune process is still active checking process gain, even though “T” is not lit. It does not affect keyboard operation.

CURRENT ACCUTUNE PROCESS ABORTED—Caused by one of the following conditions: changing to manual mode, digital input detected, in heat region of output but a cool output was calculated, or vice versa.

SP2—LSP2 not configured or a Setpoint other than LSP1 or LSP2 is in use.

32

UDC3200 Universal Digital Controller Operator Manual

04/08

Page 38
Image 38
Honeywell UDC3200 manual Accutune Set Up Group, Fuzzy Disable Enable Accutune Tune, AT Error