
3.10 Control Set Up Group
Function | Selections or |
Prompt | Range of Setting |
Lower Display | Upper Display |
PV SOURCE |
|
| INPUT 1 |
| INPUT 2 |
| IN ALG1 |
|
|
PID SETS |
|
1 ONLY
2KEYBD
Lower
Display
Parameter Definition
PROCESS VARIABLE SOURCE
INPUT 1
INPUT 2
INPUT ALGORITHM 1
NUMBER OF TUNING PARAMETER
ONE SET
TWO SETS KEYBOARD
Press this key until you see PID SET1 or PID SET2 then press
or
to switch between sets. Configure the values for: Gain, Rate, Reset, Cycle Time, Gain #2, Rate #2, Reset #2, Cycle #2 Time
PID SETS | 2PV SW |
(continued) |
|
2SP SW
SW VALUE Value in engineering units within PV or SP range limits
LSP’S
1 ONLY TWO
THREE
TWO SETS PV AUTOMATIC
TWO SETS SP AUTOMATIC
ATTENTION Other prompts affected: SW VALUE
AUTOMATIC SWITCHOVER
LOCAL SETPOINT
LOCAL
SP
between two local setpoints using the Select key.
THREE LOCAL
SP
between three local setpoints using the Select key
48 | UDC3200 Universal Digital Controller Operator Manual | 04/08 |