Honeywell UDC3200 High Alarm, LOW Alarm, A1S1 EV, Beginning of Segment, END of Segment, A1S2TYPE

Models: UDC3200

1 90
Download 90 pages 12.89 Kb
Page 66
Image 66

Function

Prompt

Lower Display

Selections or

Range of Setting

Upper Display

Parameter Definition

regardless of whichever SP is active.

NOTE 4. Loop Break monitors the control loop to determine if it is working. When enabled, the control output is checked against the minimum and maximum output limit settings. When the output reaches one of these limits, a timer begins. If the timer expires and the output has not caused the PV to move by a pre- determined amount, then the alarm activates, thus signalling that the loop is broken. The loop break timer value must be configured by the operator as the AxSx VAL entry. This value is in seconds with a range of 0 to 3600 seconds. A setting of 0 is equivalent to an instantaneous loop break when the output reaches one of its limit values.

The amount of PV Movement required is determined by the “UNITS” setting in the Display Setup Group. For the Degrees F configuration, the PV must move by 3° in the desired direction in the time allowed. For the Degrees C configuration, the PV must move by 2° in the desired direction in the time allowed. For the “NONE” selection, the PV must move 1% of the PV range in the time allowed.

Loop Break alarms do not have a HIGH/LOW State configuration, they are always assumed to be a HIGH state alarm.

NOTE 5. Thermocouple Warning means that the instrument has detected that the Thermocouple Input is starting to fail. Not valid for other input types.

NOTE 6. Thermocouple Failing means that the instrument has detected that the Thermocouple Input is in imminent danger of failing. Not valid for other input types.

NOTE 7: For the Digital Input selections, DIG INP1 can be either enabled or disabled in the Options Group (See Sub-Section3.11), but DIG INP2 must be enabled in the Options Group for the alarm to function properly.

 

 

If Setpoint Programming is disabled or if the Alarm Type is

 

 

not configured for Event On/Off:

A1S1 H L

 

ALARM 1 SETPOINT 1 STATE—Select whether you want the

 

alarm type chosen in prompt A1S1TYPE to alarm High or Low.

 

 

 

HIGH

HIGH ALARM

 

LOW

LOW ALARM

 

 

If Setpoint Programming is enabled and if the Alarm Type is

 

 

configured for Event On/Off:

A1S1 EV

 

ALARM 1 SEGMENT EVENT 1—Select whether you want the

 

 

alarm type chosen in prompt A1S1TYPE to alarm the beginning

 

 

or end of a segment in setpoint Ramp/Soak programming.

 

BEGIN

BEGINNING OF SEGMENT

 

END

END OF SEGMENT

 

 

 

 

Alarms configured for events will not operate on

 

 

 

ATTENTION

 

 

 

Setpoint Program segments of zero length.

 

 

 

A1S2TYPE

Same as A1S1

ALARM 1 SETPOINT 2 TYPE—Select what you want Setpoint 2

 

TYPE

of Alarm 1 to represent.

 

 

The selections are the same as A1S1TYPE.

 

 

 

 

A1S2 H L

HIGH

 

ALARM 1 SETPOINT 2 STATE—Same as A1S1 H L.

 

LOW

 

 

 

 

 

 

 

 

60

UDC3200 Universal Digital Controller Operator Manual

04/08

Page 66
Image 66
Honeywell UDC3200 manual High Alarm, LOW Alarm, A1S1 EV, Beginning of Segment, END of Segment, A1S2TYPE