![](/images/new-backgrounds/1200674/20067485x1.webp)
Function | Selections or |
Prompt | Range of Setting |
Lower Display | Upper Display |
| FCC |
DEW PT
OXYGEN
Parameter Definition
CARBON POTENTIAL
DEWPOINT OF CARBONIZING
PERCENT OXYGEN
ATTENTION The Carbon and Dewpoint selections will automatically set the first input actuation to Carbon. The Oxygen selection will automatically set the first input actuation to Oxygen. Input 2 can be any input actuation, but it is normally a type K, R or S thermocouple input, depending upon the probe type selected. All calculations are performed by the Controller with Percent Carbon shown as the PV display. The actual value of each analog input may be viewed on the lower display. For all Carbon Types, if the value of Percent Carbon falls below 0.1% - such as can happen when the Carbon Probe voltage output falls below 900 mVdc – then the Controller will continue to update the PV display, but the accuracy is unspecified. Likewise, if the measured temperature falls outside of the specified ranges as noted above for the Carbon, Oxygen and Dewpoint input types, then the Controller will continue to update the PV display, but the accuracy is unspecified. For the Dewpoint algorithm, if the Carbon Sensor voltage falls below 800 mVdc, then the Dew Point is calculated as if the sensor voltage was at 800 mVdc.
MATH K | 0.001 to 1000 |
| floating |
|
|
CALC HI | |
| Floating |
| (in engineering |
| units) |
|
|
CALC LO | |
| Floating |
| (in engineering |
| units) |
|
|
ALG1 INA |
|
| INPUT 1 |
| INPUT 2 |
| OUTPUT |
|
|
WEIGHTED AVERAGE RATIO OR MASS FLOW ORIFICE CONSTANT (K) FOR MATH
CALCULATED VARIABLE HIGH SCALING FACTOR FOR INPUT ALGORITHM
CALCULATED VARIABLE LOW SCALING FACTOR FOR INPUT ALGORITHM
ALGORITHM 1, INPUT A SELECTION will represent one of the available selections.
Input 1
Input 2
Output – Should not be used for Three Position Step Control applications)
04/08 | UDC3200 Universal Digital Controller Operator Manual | 37 |