Honeywell UDC3200 manual Fcc, Math K, Calc HI, Calc LO, ALG1 INA

Models: UDC3200

1 90
Download 90 pages 12.89 Kb
Page 43
Image 43

Function

Selections or

Prompt

Range of Setting

Lower Display

Upper Display

 

FCC

DEW PT

OXYGEN

Parameter Definition

CARBON POTENTIAL FCC—Make this selection if you have a Furnace Controls Corp Accucarb type Zirconium Oxide sensor. This algorithm requires a temperature range within the region of 1380 °F to 2000 °F. See Note 3.

DEWPOINT OF CARBONIZING ATMOSPHERE—Use this selection if you are using any Zirconium Oxide Carbon Probe and you want to measure the atmosphere in terms of Dewpoint. The range is –50 °F to 100 °F or –48 °C to 38 °C. This algorithm requires a temperature range within the region of 1000 °F to 2200 °F and a minimum carbon probe value of 800 millivolts.

PERCENT OXYGEN RANGE—Make this selection if you are using a Zirconium Oxide Oxygen Probe to measure Percent of Oxygen in a range of 0 to 40 % O2. This algorithm requires a temperature range within the region of 800 °F to 3000 °F.

ATTENTION The Carbon and Dewpoint selections will automatically set the first input actuation to Carbon. The Oxygen selection will automatically set the first input actuation to Oxygen. Input 2 can be any input actuation, but it is normally a type K, R or S thermocouple input, depending upon the probe type selected. All calculations are performed by the Controller with Percent Carbon shown as the PV display. The actual value of each analog input may be viewed on the lower display. For all Carbon Types, if the value of Percent Carbon falls below 0.1% - such as can happen when the Carbon Probe voltage output falls below 900 mVdc – then the Controller will continue to update the PV display, but the accuracy is unspecified. Likewise, if the measured temperature falls outside of the specified ranges as noted above for the Carbon, Oxygen and Dewpoint input types, then the Controller will continue to update the PV display, but the accuracy is unspecified. For the Dewpoint algorithm, if the Carbon Sensor voltage falls below 800 mVdc, then the Dew Point is calculated as if the sensor voltage was at 800 mVdc.

MATH K

0.001 to 1000

 

floating

 

 

CALC HI

–999. To 9999.

 

Floating

 

(in engineering

 

units)

 

 

CALC LO

–999. To 9999.

 

Floating

 

(in engineering

 

units)

 

 

ALG1 INA

 

 

INPUT 1

 

INPUT 2

 

OUTPUT

 

 

WEIGHTED AVERAGE RATIO OR MASS FLOW ORIFICE CONSTANT (K) FOR MATH SELECTIONS—Only applicable for algorithms W AVG or General Math selections MuDIV, MULT, MuDIV, or MULT.

CALCULATED VARIABLE HIGH SCALING FACTOR FOR INPUT ALGORITHM 1—Used only when either Summer, Input Hi/Lo, or one of the General Math functions was selected as the Input Algorithm. See Note 2.

CALCULATED VARIABLE LOW SCALING FACTOR FOR INPUT ALGORITHM 1—Used only when either Summer, Input Hi/Lo, or one of the General Math functions was selected as the Input Algorithm. See Note 2.

ALGORITHM 1, INPUT A SELECTION will represent one of the available selections.

Input 1

Input 2

Output – Should not be used for Three Position Step Control applications)

04/08

UDC3200 Universal Digital Controller Operator Manual

37

Page 43
Image 43
Honeywell UDC3200 manual Fcc, Math K, Calc HI, Calc LO, ALG1 INA