3.9Input 2 Set Up Group

 

 

Function Prompt

Selections or

 

 

Parameter

 

 

 

 

Lower Display

Range of Setting

 

 

Definition

 

 

 

 

 

 

Upper Display

 

 

 

 

 

 

 

IN2 TYPE

 

 

 

INPUT 2 ACTUATION TYPE – This selection

 

 

 

 

 

 

 

 

 

determines what actuation you are going to use for

 

 

ATTENTION

 

 

 

 

Input 2.

 

 

 

 

Changing the input

 

 

 

 

 

 

 

 

 

DISABLE—Disables Input.

 

 

 

 

type will result in the

DISABLE

 

 

 

 

 

 

loss of Field

B TC

 

 

B TC—B Thermocouple

 

 

 

 

Calibration values and

E TC H

 

 

E TC H—E Thermocouple High

 

 

 

 

will restore Factory

E TC L

 

 

E TC L—E Thermocouple Low

 

 

 

 

Calibration values.

J TC H

 

 

J TC H—J Thermocouple High

 

 

 

 

 

 

J TC M

 

 

J TC M—J Thermocouple Med

 

 

 

 

Selecting Position

J TC L

 

 

J TC L—J Thermocouple Low

 

 

 

 

Proportional Control in

K TC H

 

 

K TC H—K Thermocouple High

 

 

 

 

the Output Setup

K TC M

 

 

K TC M—K Thermocouple Med

 

 

 

 

Group forces Input 2

K TC L

 

 

K TC L—K Thermocouple Low

 

 

 

 

to the Slidewire

NNM H

 

 

NNM H—Ni-Ni-Moly Thermocouple High

 

 

 

 

Selection.

NNM L

 

 

NNM L—Ni-Ni-Moly Thermocouple Low

 

 

 

 

 

 

NIC H

 

 

NIC H—Nicrosil-Nisil Thermocouple High

 

 

 

 

 

 

NIC L

 

 

NIC L—Nicrosil-Nisil Thermocouple Low

 

 

 

 

 

 

R TC

 

 

R TC—R Thermocouple

 

 

 

 

 

 

S TC

 

 

S TC—S Thermocouple

 

 

 

 

 

 

T TC H

 

 

T TC H—T Thermocouple High

 

 

 

 

 

 

T TC L

 

 

T TC L—T Thermocouple Low

 

 

 

 

 

 

W TC H

 

 

W TC H—W5W26 Thermocouple High

 

 

 

 

 

 

W TC L

 

 

W TC L—W5W26 Thermocouple Low

 

 

 

 

 

 

100 PT

 

 

100 PT—100 Ohm RTD High

 

 

 

 

 

 

100 LO

 

 

100 LO—100 Ohm RTD Low

 

 

 

 

 

 

200 PT

 

 

200 PT—200 Ohm RTD

 

 

 

 

 

 

500 PT

 

 

500 PT—500 Ohm RTD

 

 

 

 

 

 

RAD RH

 

 

RAD RH—Radiamatic RH

 

 

 

 

 

 

RAD RI

 

 

RAD RI—Radiamatic RI

 

 

 

 

 

 

0-20mA

 

 

0-20mA—0 to 20 Milliamperes

 

 

 

 

 

 

4-20mA

 

 

4-20mA—4 to 20 Milliamperes

 

 

 

 

 

 

0-10mV

 

 

0-10mV—0 to 10 Millivolts

 

 

 

 

 

 

0-50mV

 

 

0-50mV—0 to 50 Millivolts

 

 

 

 

 

 

0-100mV

 

 

0-100mV—0 to 100 Millivolts

 

 

 

 

 

 

0-5 V

 

 

0-5V—0 to 5 Volts

 

 

 

 

 

 

1-5 V

 

 

1-5V—1 to 5 Volts

 

 

 

 

 

 

0-10 V

 

 

0-10V—0 to 10 Volts

 

 

 

 

 

 

TC DIFF

 

 

TC DIFF—Thermocouple Differential

 

 

 

 

 

 

SLIDEW

 

 

SLIDEW—Slidewire (For Position Proportional

 

 

 

 

 

 

 

Applications)

 

 

 

 

XMITTER2

B TC

S TC

 

TRANSMITTER CHARACTERIZATION—This

 

 

 

 

E TC H

T TC H

 

selection lets you instruct the controller to

 

 

 

 

 

 

E TC L

T TC L

 

characterize a linear input to represent a non-linear

 

 

 

 

J TC H

W TC H

 

one.

 

 

 

 

 

 

J TC M

W TC L

 

 

Prompt only appears when a linear

 

 

 

 

J TC L

100 PT

 

ATTENTION

 

 

 

 

K TC H

100 LO

 

actuation is selected at prompt IN2 TYPE.

 

 

 

 

 

 

K TC M

200 PT

 

Parameter definitions are the same as in IN2 TYPE.

 

 

 

 

K TC L

500 PT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NNM H

RAD RH

 

 

 

 

 

 

 

 

 

NNM L

RAD RI

 

 

 

 

 

 

 

 

 

NIC H

LINEAR

 

 

 

 

 

 

 

 

 

NIC L

SQROOT

 

 

 

 

 

 

 

 

 

R TC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

04/08

 

UDC3200 Universal Digital Controller Operator Manual

45

 