Honeywell UDC3200 manual ALARM12, Diagnost

Models: UDC3200

1 90
Download 90 pages 12.89 Kb
Page 68
Image 68

Function

Selections or

 

 

Parameter Definition

Prompt

Range of Setting

 

 

 

Lower Display

Upper Display

 

 

 

 

DISABLE

DISABLE—Disables blocking

 

ALARM 1

ALARM 1—Blocks alarm 1 only

 

ALARM 2

ALARM 2—Blocks alarm 2 only

 

ALARM12

ALARM12—Blocks both alarms

 

 

 

 

When enabled on power up or initial enabling via

 

 

 

ATTENTION

 

 

 

configuration,

the alarm will not activate unless the parameter

 

 

 

being monitored has not been in an alarm condition for a

 

 

 

minimum of one control cycle (167 ms).

 

 

 

 

DIAGNOST

 

 

DIAGNOSTIC—Monitors the Current Output and/or Auxiliary

 

 

 

Output for an open circuit condition. If either of these two outputs

 

 

 

falls below about 3.5 mA, then an Alarm is activated. This

 

 

 

configuration is in addition to whatever was selected for

 

 

 

AxSxTYPE.

 

DISABLE

DISABLE—Disables Diagnostic Alarm

 

ALARM 1

ALARM 1—Alarm 1 is diagnostic alarm

 

ALARM 2

ALARM 2—Alarm 2 is diagnostic alarm

 

 

 

 

 

62

UDC3200 Universal Digital Controller Operator Manual

04/08

Page 68
Image 68
Honeywell UDC3200 manual ALARM12, Diagnost