4.5.4 Using BLENDED TUNE at start-up for Duplex (Heat/Cool)

When DUPLEX has been configured for DISABLE. This is the preferred selection for Heat/Cool applications which use a highly insulated chamber (a chamber which will lose heat very slowly unless a cooling device is applied). Only one local setpoint (LSP 1) is needed for this selection.

This selection results in performance tuning over the full range utilizing both Heat and Cool outputs to acquire blended tune values that are then applied to both Heat and Cool tuning parameters. Both PID sets are set to the same values.

Table 4-7 Procedure for Using BLENDED TUNE at Start-up for Duplex Control

Step

Operation

 

Press

Result

1

Configure LSP1

 

 

 

Until SP (Local Setpoint 1) shows

 

Lower

 

 

 

 

Display

 

in the lower display.

 

 

 

 

 

2

 

 

or

 

Until the Setpoint is to the desired

 

 

 

 

 

value.

3

Switch to

 

 

 

Until the “A” indicator is lighted (on

 

Man

 

 

“Automatic” Mode

 

Auto

 

controllers with Manual option).

 

 

 

 

 

4

Show Tuning

 

 

 

Until “TUNE OFF” is shown on

 

Lower

 

 

Prompt

 

Display

 

lower display.

 

 

 

 

 

5

Initiate Tuning

 

 

 

Select “DO SLOW” or “DO FAST”

 

 

 

 

 

in lower display.

6

Tuning in operation

 

 

 

Upper display will show a “T” as

 

Lower

 

 

 

 

Display

 

long as ACCUTUNE process is

 

 

 

 

 

operating. When process

 

 

 

 

 

completes, tuning parameters are

 

 

 

 

 

calculated and lower display will

 

 

 

 

 

show “NO TUNE” prompt.

4.5.5 Using MANUAL TUNE at start-up for Duplex (Heat/Cool)

When DUPLEX has been configured for MANUAL. This selection should be used when tuning is needed only for the HEAT zone or only for the COOL zone but not both. If Local Setpoint 1 is used, then the controller will perform a HEAT zone tune. If Local Setpoint 2 is used, then the controller will perform a COOL zone tune.

Table 4-8 Procedure for Using MANUAL TUNE for Heat side of Duplex Control

Step

Operation

 

Press

Result

1

Configure LSP1

 

 

 

Until SP (Local Setpoint 1) shows

 

Lower

 

 

 

 

Display

 

in the lower display.

 

 

 

 

 

2

 

 

or

 

Until LSP1 is a value within the

 

 

 

 

 

Heat Zone (output above 50%).

3

Switch to

 

 

 

Until the “A” indicator is lighted (on

 

Man

 

 

“Automatic” Mode

 

Auto

 

controllers with Manual option).

 

 

 

 

 

 

 

 

 

 

 

04/08

UDC3200 Universal Digital Controller Operator Manual

75

Page 81