3.2 Configuration Procedure

Introduction

Each of the Set Up groups and their functions are pre-configured at the factory. If you want to change any of these selections or values, follow the procedure in Table 3-1.This procedure tells you the keys to press to get to any Set Up group and any associated Function parameter prompt.

Procedure

ATTENTION

The prompting scrolls at a rate of 2/3 seconds when the SET UP or FUNCTION key is held in.

Also, or keys will move group prompts forward or backward at a rate twice as fast.

Table 3-1 Configuration Procedure

Step

Operation

 

Press

 

 

Result

1

Enter Set Up

 

 

 

Upper Display = SETUP

 

Setup

 

 

Mode

 

 

Lower Display = TUNING (This is the first Set Up Group title)

 

 

 

 

2

Select any Set

 

 

 

Sequentially displays the other Set Up group titles. You can also

 

Setup

 

 

Up Group

 

 

use the

or

keys to scan the Set Up groups in both

 

 

 

 

 

 

 

 

 

directions. Stop at the Set Up group title that describes the group of

 

 

 

 

 

parameters you want to configure. Then proceed to the next step.

3

Select a Function

Function

 

Parameter

 

 

4

Change the

or

 

Value or

 

 

Selection

 

5

Enter the Value

Function

 

or Selection

 

 

6

Exit Configuration

Lower

 

 

Display

Upper Display = the current value or selection for the first function prompt of the selected Set Up group.

Lower Display = the first Function prompt within that Set Up group. Sequentially displays the other function prompts of the Set Up group you have selected. Stop at the function prompt that you want to change, then proceed to the next step.

Increments or decrements the value or selection that appears for the selected function prompt. If you change the value or selection of a parameter while in Set Up mode but then decide not to enter it, press the MAN/AUTO key once. This will recall the original configuration. This “recall” procedure does not work for a Field Calibration process. Field Calibration is a one-way operation.

Enters value or selection made into memory after another key is pressed.

Exits configuration mode and returns controller to the same state it was in immediately preceding entry into the Set Up mode. It stores any changes you have made.

If you do not press any keys for 30 seconds, the controller times out and reverts to the mode and associated display used prior to entry into Set Up mode.