Chapter 12. Protective functions
12.1 Electronic Thermal
|
|
|
|
|
|
|
|
|
|
| Group |
|
| LED |
|
| Parameter Name |
| Set |
|
|
| display |
|
|
| value | ||
|
|
|
|
|
|
|
| ||
Function |
| F50 |
|
| [Electronic thermal |
| 1 | ||
group 1 |
|
|
| select] |
| ||||
|
|
|
|
|
| ||||
|
|
| F51 |
| [Electronic thermal level for | - | |||
|
|
|
| 1 minute] | |||||
|
|
|
|
|
|
|
| ||
|
|
| F52 |
| [Electronic thermal level for | - | |||
|
|
|
| continuous] | |||||
|
|
|
|
|
|
|
| ||
|
|
| F53 |
| [Motor type] | - | |||
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
Min/Max setting
0/1
50/150
0/1
| Factory |
|
| Unit |
|
| default |
|
|
| |
|
|
|
|
| |
0 |
|
|
|
| |
|
|
|
| ||
150 |
| % |
|
100%
Select F50 – [Electronic thermal select] to 1.
It activates when the motor is overheated
F51: Enter the value of max current that is capable of flowing to the motor continuously for one minute. It is set in percent of motor rated current. The value cannot be set lower than F52.
F52: Enter the amount of current for continuous operation. Normally motor rated current is used. It cannot be set greater than F51.
F53: For an inductance motor, cooling effects decrease when a motor is running at low speed. A special motor is a motor that uses a separately powered cooling fan maximize cooling effect even in low speed. Therefore, as the motor speed changes, the cooling does not change.
F53
[Motor type]
0
1
Standard motors having a cooling fan directly connected to the shaft
Special motor that uses a separately powered cooling fan.
Current for |
|
continuous [%] | H53 = 1 |
100 |
|
95 | H53 = 2 |
| |
65 |
|
| Freq [Hz] |
20 | 60 |
Current [%]
F51 |
|
F52 |
|
60 | ETH trip time [sec] |
110