Chapter 12. Protective functions
12.2 Overload Warning and trip
zOverload warning
|
| Group |
|
| LED |
|
| Parameter Name |
|
| Set |
|
| Min/Max |
|
| Factory |
|
| Unit |
|
|
|
|
| Display |
|
|
|
| value |
|
| setting |
|
| default |
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
| Function |
| F54 |
|
| [Overload warning |
| - |
| 30/150 |
| 150 |
| % |
| ||||||
| group 1 |
|
|
| level] |
|
|
|
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
| F55 |
|
| [Overload warning time] |
|
| - |
| 0/30 |
| 10 |
|
| Sec | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
| I/O group |
| I54 |
|
|
|
| 5 |
| 0/17 |
| 12 |
|
|
|
| |||||
|
|
|
|
|
|
| terminal select] |
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
| I55 |
| 5 |
|
|
|
| 17 |
|
|
|
| |||||
|
|
|
|
|
| select] |
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Select one output terminal for this function between MO and 30AC.
If selecting MO as output terminal, set I54 to 5 {Overload: OL}.
F54: Set the value as a percent of motor rated current.
| t : Overload |
|
t | warning time | t |
Current |
| F54 |
|
| |
|
|
|
output |
|
|
zOverload trip
Group | LED | Parameter Name | Set | |
Display | value | |||
|
|
Function |
| F56 |
| [Overload trip select] |
| 1 |
| |
group 1 |
|
|
|
|
| |||
|
|
|
|
|
|
| ||
|
|
| F57 | [Overload trip level] | - |
| ||
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
| F58 | [Overload trip time] | - |
| ||
|
|
|
|
|
Min/Max setting
0/1
30/200
0/60
| Factory |
| Unit |
|
| default |
|
| |
|
|
|
| |
|
|
|
|
|
0 |
|
|
|
180%
60sec
Set F56 to 1.
Inverter output is turned off when motor is overloaded.
Inverter output is turned off when excessive current flows to the motor for F58 – [Overload trip time].
111