Chapter 13. Troubleshooting & Maintenance
13.Troubleshooting & Maintenance
13.1 Protective functions
WARNING
When a fault occurs, the cause must be corrected before the fault can be cleared. If protective function keeps active, it could lead to reduction in product life and damage to the equipment.
Fault Display and information
Keypad | Protective | Descriptions | ||
display | functions | |||
| ||||
| Over current | The inverter turns off its output when the output current of the inverter flows more | ||
| than 200% of the inverter rated current. | |||
| Ground | fault | The inverter turns off its output when a ground fault occurs and the ground fault | |
| current |
| current is more than the internal setting value of the inverter. | |
| Inverter |
| The inverter turns off its output when the output current of the inverter flows more | |
| Overload |
| than the rated level (150% for 1 minute). | |
| Overload trip | The inverter turns off its output if the output current of the inverter flows at 150% of | ||
| the inverter rated current for more than the current limit time (1 min). | |||
| Heat | sink | The inverter turns off its output if the heat sink overheats due to a damaged cooling | |
| fan or an alien substance in the cooling fan by detecting the temperature of the heat | |||
| overheat |
| ||
|
| sink. | ||
|
|
| ||
| DC | link | The inverter turns off its output when it is time to replace the old DC link capacitor to a | |
| capacitor |
| new one. | |
| overload |
| The inverter turns off its output when the one or more of the output (U, V, W) phase is | |
| Output | Phase | ||
| loss |
| open. The inverter detects the output current to check the phase loss of the output. | |
|
|
| The inverter turns off its output if the DC voltage of the main circuit increases higher | |
| Over voltage | than 400 V when the motor decelerates. This fault can also occur due to a surge | ||
|
|
| voltage generated at the power supply system. | |
|
|
| The inverter turns off its output if the DC voltage is below 180V because insufficient | |
| Low voltage | torque or overheating of the motor can occur when the input voltage of the inverter | ||
|
|
| drops. | |
| Electronic | The internal electronic thermal of the inverter determines the overheating of the | ||
| motor. If the motor is overloaded the inverter turns off the output. The inverter cannot | |||
| Thermal |
| ||
|
| protect the motor when driving a motor having more than 4 poles or multi motors. | ||
|
|
| ||
| Parameter | This fault message is displayed when | ||
| save error | memory. |
Keypad | Protective | Descriptions | ||
display | functions | |||
| ||||
| Inverter |
| This fault message is displayed when an error occurs in the control circuitry of the | |
| hardware fault | inverter. | ||
| Communication | This fault message is displayed when the inverter cannot communicate with the | ||
| Error |
| keypad. | |
| Cooling | fan | This fault message is displayed when a fault condition occurs in the inverter cooling | |
| fault |
| fan. | |
| Instant cut off | Used for the emergency stop of the inverter. The inverter instantly turns off the output | ||
| when the EST terminal is turned on. | |||
|
|
|
117