Chapter 13. Troubleshooting & Maintenance

13.Troubleshooting & Maintenance

13.1 Protective functions

WARNING

When a fault occurs, the cause must be corrected before the fault can be cleared. If protective function keeps active, it could lead to reduction in product life and damage to the equipment.

Fault Display and information

Keypad

Protective

Descriptions

display

functions

 

 

Over current

The inverter turns off its output when the output current of the inverter flows more

 

than 200% of the inverter rated current.

 

Ground

fault

The inverter turns off its output when a ground fault occurs and the ground fault

 

current

 

current is more than the internal setting value of the inverter.

 

Inverter

 

The inverter turns off its output when the output current of the inverter flows more

 

Overload

 

than the rated level (150% for 1 minute).

 

Overload trip

The inverter turns off its output if the output current of the inverter flows at 150% of

 

the inverter rated current for more than the current limit time (1 min).

 

Heat

sink

The inverter turns off its output if the heat sink overheats due to a damaged cooling

 

fan or an alien substance in the cooling fan by detecting the temperature of the heat

 

overheat

 

 

 

sink.

 

 

 

 

DC

link

The inverter turns off its output when it is time to replace the old DC link capacitor to a

 

capacitor

 

new one.

 

overload

 

The inverter turns off its output when the one or more of the output (U, V, W) phase is

 

Output

Phase

 

loss

 

open. The inverter detects the output current to check the phase loss of the output.

 

 

 

The inverter turns off its output if the DC voltage of the main circuit increases higher

 

Over voltage

than 400 V when the motor decelerates. This fault can also occur due to a surge

 

 

 

voltage generated at the power supply system.

 

 

 

The inverter turns off its output if the DC voltage is below 180V because insufficient

 

Low voltage

torque or overheating of the motor can occur when the input voltage of the inverter

 

 

 

drops.

 

Electronic

The internal electronic thermal of the inverter determines the overheating of the

 

motor. If the motor is overloaded the inverter turns off the output. The inverter cannot

 

Thermal

 

 

 

protect the motor when driving a motor having more than 4 poles or multi motors.

 

 

 

 

Parameter

This fault message is displayed when user-setting parameters fails to be entered into

 

save error

memory.

Keypad

Protective

Descriptions

display

functions

 

 

Inverter

 

This fault message is displayed when an error occurs in the control circuitry of the

 

hardware fault

inverter.

 

Communication

This fault message is displayed when the inverter cannot communicate with the

 

Error

 

keypad.

 

Cooling

fan

This fault message is displayed when a fault condition occurs in the inverter cooling

 

fault

 

fan.

 

Instant cut off

Used for the emergency stop of the inverter. The inverter instantly turns off the output

 