Chapter 9. Basic functions

zAccel/Decel time based on Run frequency

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Group

 

 

LED display

 

 

Parameter name

 

 

Set

 

 

 

 

 

 

 

 

value

 

 

 

 

 

 

 

 

 

 

 

 

 

Drive

 

ACC

[Accel time]

 

 

-

 

group

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

dEC

 

[Decel time]

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Function

 

H70

 

 

[Frequency

reference

 

 

1

 

group 2

 

 

 

for Accel/Decel]

 

 

 

 

 

 

 

 

 

 

 

Min/Max

range

0/6000

0/6000

0/1

 

Factory

 

Unit

 

 

defaults

 

 

 

 

 

 

5.0sec

10.0sec

0

ƒAccel/Decel time is set at the ACC/dEC.

ƒIf you set H70 to 1 {Delta frequency}, Accel/Decel time is the time that takes to reach a target freq from run freq (Currently operating freq.).

When H70 and Accel time are set to 1 {Delta frequency} and 5 sec, respectively,

(A zone: run freq 10 Hz applied first, B zone: Operating via 10 Hz, different run freq is not issued

C:30Hz Run freq (in this case, Target freq) issued while 10 Hz run freq is applied. But the preset accel time 5 sec is maintained. )

Freq.

 

 

30Hz

 

 

(Target freq.)

command

 

 

(Run freq.)

(Delta freq.)

10Hz

A

B

C

Time

5

7

12

[sec]

Run

 

 

 

command

 

 

 

5 sec

 

5 sec

 

71