Chapter 9. Basic functions

9.5V/F control

z Linear V/F operation

Group

LED Display

Parameter Name

Set

Value

 

 

 

Function

 

F22

 

[Base frequency]

-

 

group 1

 

 

 

 

 

 

 

 

 

 

F23

 

[Start frequency]

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F30

 

[V/F pattern]

0

 

 

 

 

 

 

 

 

Min/Max

Range

30/400

0/10.0

0/2

 

Factory

 

Unit

 

 

Defaults

 

 

 

 

 

 

60.0Hz

0.5Hz

0

ƒSet F30 to 0 {Linear}.

ƒThis pattern maintains a linear Volts/frequency ratio from F23 - [Start frequency] to F22- [Base frequency]. This is appropriate for constant torque applications.

F22 – [Base frequency]: Inverter outputs its rated voltage at this level. Enter the motor nameplate frequency.

F23 – [Start frequency]: Inverter starts to output its voltage at this level.

 

 

 

Base freq.

 

 

 

 

 

 

Freq.

Start freq.

 

 

 

 

 

 

 

 

 

 

 

 

 

Inverter rated

 

 

 

 

 

 

 

voltage

 

 

 

 

 

 

 

Voltage

 

 

 

 

 

 

 

Run

 

 

 

 

 

 

 

command

 

 

 

 

 

z

Square V/F operation

 

 

 

 

 

 

Group

LED Display

Parameter Name

Set

Min/Max

Factory

Unit

 

Value

Range

Defaults

Function

 

 

 

F30

[V/F pattern]

1

0/2

0

 

 

group 1

 

 

 

 

 

 

 

 

ƒ Set F30 to 1{Square}.

 

 

 

 

 

ƒ

This pattern maintains squared volts/hertz ratio. Appropriate applications are fans, pumps, etc.

 

Voltage

100%

Freq.

Base freq.

75

Page 75