10. Advanced functions

10.12 Auto restart try

 

Group

 

 

LED Display

 

 

Parameter Name

 

 

 

Set

 

 

Min/Max

 

 

Factory

 

 

Unit

 

 

 

 

 

 

 

 

 

value

 

 

Range

 

 

Defaults

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Function

 

H26

 

 

[Number of Auto Restart

 

 

 

-

 

0/10

 

0

 

 

 

 

group 2

 

 

 

try]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H27

 

[Auto Restart time]

-

 

0/60

 

1.0

 

 

Sec

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ƒThis parameter sets the number of times auto restart is activated in H26.

ƒIt is used to prevent the system down caused by internal protection function activated by the causes such as noise.

H26: Auto restart will become active after the H27. H26 – [Number of Auto restart try] is reduced by 1 when it is active. If the trip outnumbers the preset restart try, auto restart function is deactivated. If the setting is reset via the control terminal or the STOP/RST key on the keypad, the number of auto restart try set by user is automatically entered.

If the trip does not occur for 30 sec after Auto restart operation, the H26 is restored to the preset value.

When operation is stopped due to Low voltage {Lvt} or Emergency stop {EST}, Auto restart will be deactivated.

After the H27- [Auto Restart time], the motor starts acceleration automatically via speed search (H22-25).

The following pattern is shown when the H26 – [Number of auto restart try] is set to 2.

Constant R un

Freq

Voltage

Speed Search operation

R eset

R un

C om m and

30Sec

N um ber of A uto

2

1

restart try

 

 

Trip occurred

H 27

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

1

0

2

 

 

94