Chapter 12. Protective functions

12.5 External trip signal

Group

I/O group

LED

Description

Set

display

Value

 

 

I20

 

[Multi-function input

 

 

 

 

 

terminal P1 define]

 

 

 

 

 

 

 

 

 

 

~

 

~

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I23

 

 

[Multi-function input

 

 

18

 

 

 

 

terminal P4 define]

 

 

 

 

 

 

 

 

 

 

 

 

I24

 

 

[Multi-function input

 

19

 

 

 

 

terminal P5 define]

 

 

 

 

 

 

 

 

 

Min/Max setting

0/24

 

 

 

 

 

 

 

Factory

 

 

Unit

 

 

default

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

ƒSelect a terminal among P1 thru P5 to output external trip signal.

ƒSet I23 and I24 to 18 and 19 to define P4 and P5 as External A contact and B contact.

External trip signal input A contact (N.O): This is a normally open contact input. When a P4 terminal set to “Ext trip-A” is ON, inverter displays the fault and turns off its output.

External trip signal input B contact (N.C): This is a normally closed contact input. When a terminal set to “Ext trip-B” is OFF, inverter displays the fault and turns off its output.

P1

FX : I20 = 0

 

 

P4

N.O.

:

I23

=

18

P5

N.C.

:

I24

=

19

CM

 

 

 

 

 

Frequency

P4(A contact)

P5(B contact) Run

command

114

Page 114
Image 114