Chapter 10. Advanced functions

10.2 Jog operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Group

 

 

LED display

 

 

Parameter name

 

 

Set

 

 

 

 

 

 

 

 

value

 

 

 

 

 

 

 

 

 

 

 

 

 

Function

 

F20

 

 

Jog frequency

 

 

 

-

 

group 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I/O group

 

I22

 

 

[Multi-function

input

 

 

4

 

 

 

 

 

 

 

terminal P3 define]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Min/Max

range

0/400

0/24

 

Factory

 

Unit

 

 

defaults

 

 

 

 

 

 

10.0Hz

2

ƒSet the desired jog frequency in F20.

ƒSelect the terminal among the Multi-function input terminal P1 thru P5 to use for this setting.

ƒIf P3 is set for Jog operation, set I22 to 4 {Jog}.

ƒJog frequency can be set within the range of F21 - [Max frequency] and F22 – [Start frequency].

P1

FX : I20 = 0

P3

JOG : I22=4

CM

 

F20

Frequency

P3 (JOG)

Run

command(FX)

Jog operation overrides all other operations except Dwell operation. Therefore, if Jog frequency command is entered in the middle of Multi-Step, Up-Down or 3-wire operation, operation is executed at Jog frequency.