Chapter 7. Function list
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Function group 2 | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| LED | Parameter | Min/Max |
|
|
|
| Description |
|
| Factory | Adjustable |
| Page |
| ||||||
| display | Name | Range |
|
|
|
|
|
| defaults | during run |
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
| H31 | [Number of | 2/12 | | This setting is displayed via rPM in | - |
| X |
|
|
| ||||||||||
|
|
| motor poles] |
|
|
| drive group. |
|
|
|
|
|
|
|
|
|
|
| |||
| H32 | [Rated slip | 0/10 |
|
|
|
| ⎛ rpm ⋅ P ⎞ |
|
|
| X |
|
|
| ||||||
|
|
| frequency] | [Hz] |
|
| f s | = f r − ⎜ |
|
|
| ⎟ |
| 2) |
|
|
|
|
| ||
|
|
|
|
|
| 120 |
|
|
|
|
| ||||||||||
|
|
|
|
| |
|
| ⎝ |
| ⎠ |
| Automatically |
|
|
|
|
| ||||
|
|
|
|
|
| Where, | fs = Rated slip frequency |
| set |
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||
|
|
|
|
|
|
| fr = Rated frequency |
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
| rpm = Motor nameplate RPM |
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
| P = Number of Motor poles |
|
|
|
|
|
|
| ||||||
| H33 | [Motor rated | 1.0/20 | | Enter motor rated current on the |
| - |
| X |
|
|
| |||||||||
|
|
| current] | [A] |
|
| nameplate. |
|
|
|
|
|
|
|
|
|
|
| |||
| H34 | [No Load | 0.1/12 | | Enter the current value detected |
| - |
| X |
| |||||||||||
|
|
| Motor | [A] |
|
| when the motor is rotating in rated rpm |
|
|
|
|
|
|
| |||||||
|
|
| Current] |
|
|
| after the load connected to the motor |
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
| shaft is removed. |
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
| Enter the 50% of | the rated current |
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
| value when it is difficult to measure H34 |
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
| - [No Load Motor Current]. |
|
|
|
|
|
|
| |||||||
| H36 | [Motor | 50/100 | | Enter the motor efficiency (see motor |
| - |
| X |
|
|
| |||||||||
|
|
| efficiency] | [%] |
|
| nameplate). |
|
|
|
|
|
|
|
|
|
|
| |||
| H37 | [Load inertia | 0/2 | | Select one of the following according | 0 |
| X |
| ||||||||||||
|
|
| rate] |
|
|
| to motor inertia. |
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
| 0 |
|
| Less than 10 times that of |
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
| motor inertia |
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
| 1 |
|
| About 10 times that of motor |
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
| inertia |
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
| 2 |
|
| More than 10 times that of |
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
| motor inertia |
|
|
|
|
|
|
|
|
|
| ||
| H39 | [Carrier | 1/15 | | This | parameter affects the audible | 3 |
| O | 10- |
| ||||||||||
|
|
| frequency | [kHz] |
|
| sound of the motor, noise emission from |
|
|
|
| 16 |
| ||||||||
|
|
| select] |
|
|
| the inverter, inverter temp, and leakage |
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
| current. If the value is set higher, the |
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
| inverter sound is quieter but the noise |
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
| from the inverter and leakage current will |
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
| become greater. |
|
|
|
|
|
|
|
|
|
|
| |||
| H40 | [Control | 0/3 | 0 |
|
| {Volts/frequency Control} | 0 |
| X |
| ||||||||||
|
|
| mode select] |
| 1 |
|
| {Slip compensation control} |
|
|
|
|
| ||||||||
|
|
|
|
| 2 |
|
| {PID Feedback control} |
|
|
|
|
| ||||||||
|
|
|
|
| 3 |
|
| {Sensorless vector control} |
|
|
|
|
| ||||||||
| H41 | [Auto tuning] | 0/1 | | If this | parameter is set to 1, it | 0 |
| X | 10- |
| ||||||||||
|
|
|
|
|
|
| automatically measures parameters of |
|
|
|
| 10 |
| ||||||||
|
|
|
|
|
|
| the H42 and H43. |
|
|
|
|
|
|
|
|
|
| ||||
| H42 | [Stator | 0/5.0[Ω] | | This is the value of the motor stator | - |
| X |
|
|
| ||||||||||
|
|
| resistance |
|
|
| resistance. |
|
|
|
|
|
|
|
|
|
|
| |||
|
|
| (Rs)] |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| H44 | [Leakage | 0/300.0 | | This is leakage inductance of the | - |
| X |
|
|
| ||||||||||
|
|
| inductance | [mH] |
|
| stator and rotor of the motor. |
|
|
|
|
|
|
| |||||||
|
|
| (Lσ)] |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| H45 |
| Sensorless P | 0/32767 | | P gain for Sensorless control | 1000 |
| O |
|
|
| |||||||||
| 1) |
| gain |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| H46 |
| Sensorless I |
| | I gain for Sensorless control | 100 |
| O |
|
|
| |||||||||
|
|
| gain |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| H50 |
| [PID | 0/1 | 0 |
|
| Terminal I input (0 ~ 20 mA) | 0 |
| X |
| |||||||||
|
|
| Feedback |
| 1 |
|
| Terminal V1 input (0 ~ 10 V) |
|
|
|
|
|
|
| ||||||
|
|
| select] |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1): Set H40 to 2 (PID control) or 3(Sensorless vector control) to display these parameters.