Chapter 7. Function list
Function group 2
| LED | Parameter | Min/Max |
| Description |
| Factory | Adjustable |
| Page |
|
| display | name | range |
|
| defaults | during run |
|
| ||
|
|
|
|
|
|
| |||||
| H 0 | [Jump code] | 1/95 |
| This parameter sets the code number to | 1 | O |
| |||
|
|
|
|
| jump. |
|
|
|
|
| |
| H 1 | [Fault history | - |
| This parameter stores information on the | nOn | - |
| |||
|
| 1] |
|
| types of faults, the frequency, the current |
|
|
|
|
| |
| H 2 | [Fault history | - |
| and the Accel/Decel condition at the time of | nOn | - |
|
|
| |
|
| 2] |
|
| fault. |
|
|
|
|
| |
| H 3 | [Fault history | - |
| The last fault is automatically stored in | nOn | - |
|
|
| |
|
| 3] |
|
| the H 1- [Fault history 1]. |
|
|
|
|
| |
| H 4 | [Fault history | - |
|
|
| nOn | - |
|
|
|
|
| 4] |
|
|
|
|
|
|
|
|
|
| H 5 | [Fault history | - |
|
|
| nOn | - |
|
|
|
|
| 5] |
|
|
|
|
|
|
|
|
|
| H 6 | [Reset fault | 0/1 |
| This parameter clears the fault history | 0 | O |
|
|
| |
|
| history] |
|
| saved in H |
|
|
|
|
| |
| H 7 | [Dwell | F23/400 |
| When run frequency is issued, motor | 5.0 | X |
| |||
|
| frequency] | [Hz] |
| starts to accelerate after dwell frequency is |
|
|
|
|
| |
|
|
|
|
| applied to the motor during H8- [Dwell time]. |
|
|
|
|
| |
|
|
|
|
| [Dwell frequency] can be set within the |
|
|
|
|
| |
|
|
|
|
| range of F21- [Max frequency] and F23- |
|
|
|
|
| |
|
|
|
|
| [Start frequency]. |
|
|
|
|
| |
| H 8 | [Dwell time] | 0/10 [sec] |
| This parameter sets the time for dwell | 0.0 | X |
|
|
| |
|
|
|
|
| operation. |
|
|
|
|
| |
| H10 | [Skip | 0/1 |
| This parameter sets the frequency range | 0 | X |
| |||
|
| frequency |
|
| to skip to prevent undesirable resonance |
|
|
|
|
| |
|
| select] |
|
| and vibration on the structure of the |
|
|
|
|
| |
|
|
|
|
| machine. |
|
|
|
|
| |
| H11 | [Skip | 0/400 |
| Run frequency cannot be set within the | 10.0 | X |
|
|
| |
| 1) | frequency low | [Hz] |
| range of H11 thru H16. |
|
|
|
|
| |
|
| limit 1] |
|
| The frequency values of the low |
|
|
|
|
| |
| H12 | [Skip |
|
| numbered parameters cannot be set above | 15.0 | X |
|
|
| |
|
| frequency high |
|
| those of the high numbered ones. |
|
|
|
|
| |
|
| limit 1] |
|
|
|
|
|
|
|
|
|
| H13 | [Skip |
|
|
|
| 20.0 | X |
|
|
|
|
| frequency low |
|
|
|
|
|
|
|
|
|
|
| limit 2] |
|
|
|
|
|
|
|
|
|
| H14 | [Skip |
|
|
|
| 25.0 | X |
|
|
|
|
| frequency high |
|
|
|
|
|
|
|
|
|
|
| limit 2] |
|
|
|
|
|
|
|
|
|
| H15 | [Skip |
|
|
|
| 30.0 | X |
|
|
|
|
| frequency low |
|
|
|
|
|
|
|
|
|
|
| limit 3] |
|
|
|
|
|
|
|
|
|
| H16 | [Skip |
|
|
|
| 35.0 | X |
|
|
|
|
| frequency high |
|
|
|
|
|
|
|
|
|
|
| limit 3] |
|
|
|
|
|
|
|
|
|
| H17 | 1/100 [%] | Set the speed reference value to form a curve | 40 | X |
| |||||
|
| accel/decel |
|
| at the start during accel/decel. If it is set |
|
|
|
|
| |
|
| start side |
|
| higher, linear zone gets smaller. |
|
|
|
|
| |
| H18 | 1/100 [%] | Set the speed reference value to form a curve | 40 | X |
|
|
| |||
|
| accel/decel |
|
| at the end during accel/decel. If it is set |
|
|
|
|
| |
|
| end side |
|
| higher, linear zone gets smaller. |
|
|
|
|
| |
| H19 | [Output phase | 0/1 |
| Inverter turns off the output when the | 0 | O |
| |||
|
| loss protection |
|
| phase of the inverter output (U, V, W) is not |
|
|
|
|
| |
|
| select] |
|
| properly connected. |
|
|
|
|
| |
| H20 | [Power On | 0/1 |
| This parameter is activated when drv is | 0 | O |
| |||
|
| Start select] |
|
| set to 1 or 2 (Run/Stop via Control terminal). |
|
|
|
|
| |
|
|
|
|
| Motor starts acceleration after AC power |
|
|
|
|
| |
|
|
|
|
| is applied while FX or RX terminal is ON. |
|
|
|
|
| |
| H21 | [Restart after | 0/1 |
| This parameter is active when drv is set | 0 | O |
|
|
| |
|
| fault reset] |
|
| to 1 or 2 (Run/Stop via Control terminal). |
|
|
|
|
| |
|
|
|
|
| Motor accelerates after the fault condition |
|
|
|
|
| |
|
|
|
|
| is reset while the FX or RX terminal is ON. |
|
|
|
|
|
47