Chapter 12. Protective functions

12.6 Inverter Overload

Inverter overload prevention function is activated when the current above inverter rated current flows.

Multi-function output terminal (MO) or Multi-function relay (30AC) is used as the alarm signal output during inverter overload trip.

Group

I/O group

 

 

 

 

 

LED

 

Parameter Name

 

Set

display

 

 

value

 

 

 

I54

 

[Multi-function output

7

 

terminal select]

 

 

 

I55

 

[Multi-function relay

7

 

select]

 

 

 

Min/Max Range

0/17

 

 

 

 

Factory

 

Unit

 

default

 

 

 

 

 

12

 

 

 

 

 

 

 

17

 

 

 

 

 

 

 

12.7 Frequency command loss

Group

I/O group

 

 

 

 

 

 

 

 

 

 

LED

 

 

Parameter Name

 

 

Set

 

 

display

 

 

 

 

value

 

 

 

 

 

 

 

 

 

I16

 

 

[Criteria for analog

 

0

 

 

 

 

input signal loss]

 

 

 

 

 

 

 

 

 

 

I62

 

 

[Drive mode select after

 

-

 

 

 

 

loss of frequency

 

 

 

 

 

 

command]

 

 

 

 

I63

 

 

[Wait time after loss of

 

 

-

 

 

 

 

frequency command]

 

 

 

 

 

 

 

 

 

 

 

 

I54

 

[Multi-function output

11

 

 

 

terminal select]

 

 

 

 

 

 

 

 

 

I55

 

[Multi-function relay

11

 

 

 

select]

 

 

 

 

 

 

 

 

Min/Max setting

0/2

0/2

1/12

0/17

 

Factory

 

Unit

 

 

default

 

 

 

 

 

 

0

 

 

 

 

 

 

 

0

 

 

 

1.0Sec

12

17

ƒSelect the Drive mode when frequency reference set via V1 and I or (V1+I) input terminal or communication option is lost.

I16: This is to set the criteria for analog input signal loss when frequency reference is given by V1, I, V 1+I or Communication option.

I16

[Criteria for analog input signal loss]

0

1

2

Disabled (Does not check the analog input signal loss)

When less than the value set in I 2, I 7, I 12 is entered

When below the value set in I 2, I 7, I 12 is entered

EX 1) The inverter determines that the freq reference is lost when DRV- Frq is set to 3 (Analog V1 input), I 16 to 1 and analog input signal is less than half of the minimum value set in I 7.

EX 2) The inverter determines that the freq reference is lost when DRV- Frq is set to 6 (V1+I), I 16 to 2 and V1 input signal is either below the minimum value set in I 7 or I input value is less than the I 12 value.

115

Page 115
Image 115
LG Electronics C Series manual Inverter Overload, Frequency command loss, Min/Max Range Factory Unit Default