10. Advanced functions

10.9 Sensorless vector control

 

Group

 

 

LED Display

 

 

Parameter Name

 

 

 

Set

 

 

Min/Max

 

 

Factory

 

 

Unit

 

 

 

 

 

 

 

 

 

value

 

 

Range

 

 

Defaults

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Function

 

H40

 

 

[Control mode select]

 

 

 

3

 

0/3

 

0

 

-

 

group 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H30

 

[Motor type select]

-

 

0.2/2.2

 

-

 

 

kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H32

 

[Rated

-

 

0/10

 

-

 

 

Hz

 

 

 

 

 

slip frequency]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H33

 

[Motor rated current]

-

 

1.0/12

 

-

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H34

 

[Motor No Load Current]

-

 

0.1/12

 

-

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H42

 

[Stator resistance (Rs)]

-

 

0/14.0

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H44

 

[Leakage inductance

-

 

0/300.00

 

-

 

 

mH

 

 

 

 

 

(Lσ)]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F14

 

[Time for energizing a

-

 

0.0/60.0

 

1.0

 

 

Sec

 

 

 

 

 

motor]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ƒIf H40 – [Control mode select] is set to 3, Sensorless vector control will become active.

Caution :

Motor parameters should be measured for high performance. It is highly recommended H41 – [Auto tuning] be done prior to proceeding operation via Sensorless vector control.

Ensure that the following parameters are entered correctly for high performance in Sensorless vector control.

H30: Select motor type connected to inverter output.

H32: Enter rated slip frequency based on motor nameplate RPM and rated frequency.

H33: Enter motor nameplate rated current.

H34: After removing the motor load, select H40 – [Control mode select] to 0 {V/F control} and run the motor at 60Hz. Enter the current displayed in Cur-[Output current] as motor no load current. If it is difficult to remove the load from the motor shaft, enter the value either 40 to 50% of the H33 – [Motor rated current] or the factory default. H42, H44: Enter the value of the parameter measured during H41 – [Auto tuning] or the factory default.

F14: This parameter accelerates the motor after pre-excitating the motor for the set time. The amount of the excitating current is set in H34- [Motor no load current].