10. Advanced functions
10.9 Sensorless vector control
| Group |
|
| LED Display |
|
| Parameter Name |
|
|
| Set |
|
| Min/Max |
|
| Factory |
|
| Unit |
|
|
|
|
|
|
|
|
| value |
|
| Range |
|
| Defaults |
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
Function |
| H40 |
|
| [Control mode select] |
|
|
| 3 |
| 0/3 |
| 0 |
| - |
| |||||
group 2 |
|
|
|
|
|
|
|
|
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
| H30 |
| [Motor type select] | - |
| 0.2/2.2 |
| - |
|
| kW | ||||||||||
|
|
|
|
|
|
|
|
| |||||||||||||
|
|
|
|
|
|
|
|
|
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
| H32 |
| [Rated | - |
| 0/10 |
| - |
|
| Hz | |||||||
|
|
|
|
| slip frequency] |
|
|
|
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
| H33 |
| [Motor rated current] | - |
| 1.0/12 |
| - |
|
| A | |||||||
|
|
|
|
|
|
|
|
|
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
| H34 |
| [Motor No Load Current] | - |
| 0.1/12 |
| - |
|
| A | |||||||
|
|
|
|
|
|
|
|
|
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
| H42 |
| [Stator resistance (Rs)] | - |
| 0/14.0 |
| - |
|
| Ω | |||||||
|
|
|
|
|
|
|
|
|
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
| H44 |
| [Leakage inductance | - |
| 0/300.00 |
| - |
|
| mH | |||||||
|
|
|
|
| (Lσ)] |
|
|
|
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
| F14 |
| [Time for energizing a | - |
| 0.0/60.0 |
| 1.0 |
|
| Sec | |||||||
|
|
|
|
| motor] |
|
|
|
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
If H40 – [Control mode select] is set to 3, Sensorless vector control will become active.
Caution :
Motor parameters should be measured for high performance. It is highly recommended H41 – [Auto tuning] be done prior to proceeding operation via Sensorless vector control.
Ensure that the following parameters are entered correctly for high performance in Sensorless vector control.
H30: Select motor type connected to inverter output.
H32: Enter rated slip frequency based on motor nameplate RPM and rated frequency.
H33: Enter motor nameplate rated current.
H34: After removing the motor load, select H40 – [Control mode select] to 0 {V/F control} and run the motor at 60Hz. Enter the current displayed in
F14: This parameter accelerates the motor after