Chapter 7. Function list

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Function group 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LED

Parameter

Min/Max

 

 

 

 

 

Description

 

 

 

 

 

 

Factory

 

Adjustable

 

Page

 

 

display

name

range

 

 

 

 

 

 

 

 

 

 

 

defaults

 

during run

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F52

[Electronic

50/150

 

 

ƒ

This

parameter

sets

the

amount

of

 

100

 

0

 

 

 

 

 

 

thermal level

[%]

 

 

 

current to keep the motor running

 

 

 

 

 

 

 

 

 

 

for continuous]

 

 

 

 

continuously.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ƒ

It cannot be

set higher

than

F51

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[Electronic thermal level for 1 minute].

 

 

 

 

 

 

 

 

 

 

F53

[Motor cooling

0/1

 

 

0

 

Standard motor having cooling fan

 

0

 

0

 

 

 

 

 

 

method]

 

 

 

 

 

directly connected to the shaft

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

A motor using a separate motor to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

power a cooling fan.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F54

[Overload

30/150

 

 

ƒ

This

parameter

sets

the

amount

of

 

150

 

0

 

12-2

 

 

 

 

warning level]

[%]

 

 

 

current to issue an alarm signal at a relay or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

multi-function output terminal (see I54, I55).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ƒ The set value is the percentage of H33-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[Motor rated current].

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F55

[Overload

0/30 [sec]

 

ƒ

This

parameter

issues

an

alarm signal

 

10

 

0

 

 

 

 

 

 

warning time]

 

 

 

 

when the current greater than F54-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[Overload warning level] flows to the motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

for F55- [Overload warning time].

 

 

 

 

 

 

 

 

 

 

 

F56

[Overload trip

0/1

 

 

ƒ

This

parameter

turns

off

the

inverter

 

1

 

0

 

12-3

 

 

 

 

select]

 

 

 

 

output when motor is overloaded.

 

 

 

 

 

 

 

 

 

 

 

F57

[Overload trip

30/200

 

 

ƒ

This

parameter

sets

the

amount

of

 

180

 

0

 

 

 

 

 

 

level]

[%]

 

 

 

overload current.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ƒ

The

value is

the percentage

of H33-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[Motor rated current].

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F58

[Overload trip

0/60 [sec]

 

ƒ

This

parameter

turns

off

the

inverter

 

60

 

0

 

 

 

 

 

 

time]

 

 

 

 

output when the F57- [Overload trip level] of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

current flows to the motor for F58- [Overload

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

trip time].

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F59

[Stall

0/7

 

 

ƒ

This parameter stops accelerating during

 

0

 

X

 

12-3

 

 

 

 

prevention

 

 

 

 

acceleration, decelerating during constant

 

 

 

 

 

 

 

 

 

 

 

 

select]

 

 

 

 

speed run and stops decelerating during

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

deceleration.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

During

 

During

 

During

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Deceleration

 

constant

 

Acceleration

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 2

 

 

Bit 1

 

 

Bit 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

-

 

 

-

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

-

 

 

-

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

-

 

 

3

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

-

 

 

3

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

3

 

 

-

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

3

 

 

-

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

3

 

 

3

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

 

3

 

 

3

 

 

 

3

 

 

 

 

 

 

 

 

 

 

F60

[Stall

30/150

 

 

ƒ

This parameter

sets the amount of

 

 

 

150

 

X

 

12-3

 

 

 

 

prevention

[%]

 

 

 

current to activate stall prevention function

 

 

 

 

 

 

 

 

 

 

 

 

level]

 

 

 

 

during Accel, constant or Decel run.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ƒ The set value is the percentage of the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H33- [Motor rated current].

 

 

 

 

 

 

 

 

 

 

 

 

 

4)

: Set F50

to 1 to display this parameter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

46